Day and Night CCH6 Installation Instructions Manual Download Page 12

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pumps

12

428 01 1703 01

Specifications subject to change without notice.

6.

If LPS or HPS trips 3 consecutive cycles, the unit
operation is locked out for 4 hours.

7.

In the event of a high pressure switch trip or high
pressure lockout, check the refrigerant charge outdoor
fan operation and outdoor coil for airflow restrictions.

8.

In the event of a low pressure switch trip or low
pressure lockout, check the refrigerant charge and
indoor airflow.

Control Fault

If the outdoor unit control board has failed, the control will
flash the appropriate fault code. (See Table 6) The control
board should be replaced.

Brown Out Protection

If the line voltage is less than 187v for at least 4 seconds, the
appropriate compressor contactor and fan relay are
de-energized.
Compressor and fan operation are not allowed until voltage is
a minimum of 190v. The control will flash the appropriate fault
code (see Table 6)

230 V Brown Out Protection Defeated:

The brownout feature can be defeated if needed for severe
noisy power conditions. This defeat should always be a last
resort to solving the problem. Defeat can be initiated through
the forced defrost pins as follows:
The brownout toggle is accomplished by shorting the defrost
pins from power up with the OAT and OCT sensor connector
removed.

After 3 seconds, the status of the force defrost short and the
OAT/OCT as open will be checked. If correct, then the
brownout will be toggled.

Status code 6 shows the brownout is disabled.

Status code 5 shows the brownout is active.

After the brownout defeat is set, power down and reinstall the
OAT/OCT sensor and remove the short from the forced
defrost pins. As long as the short on the forced defrost
remains, the OAT and OCT faults will not be cleared. The
code will continue to be flashed.

The control is shipped with the brownout active. The change
in status is remembered until toggled to a new status. A
power down/power up sequence will not reset the status. It
may be necessary to do the toggle twice to cycle to the
desired state of the defeat.

230V Line (Power Disconnect) Detection

If there is no 230v at the compressor contactor(s) when the

indoor unit is powered and cooling demand exists, the

appropriate error code is displayed (see Table 6). Verify that

the disconnect is closed and 230v wiring is connected to the

unit.

Compressor Voltage Sensing

The control board input terminals labeled VS and L2 (see

Fig. 14) are used to detect compressor voltage status, and

alert the user of potential problems. The control continuously

monitors the high voltage on the run capacitor of the

compressor motor. Voltage should be present any time the

compressor contactor is energized, and voltage should not

be present when the contactor is de

energized.

Contactor Shorted Detection

If there is compressor voltage sensed when there is no

demand for compressor operation, the contactor may be

stuck closed or there is a wiring error. The control will flash

the appropriate fault code.

Compressor Thermal Cutout

If the control senses the compressor voltage after start

up,

and is then absent for 10 consecutive seconds while cooling

demand exists, the thermal protector is open. The control

de

energizes the compressor contactor for 15 minutes, but

continues to operate the outdoor fan.
The control Status LED will flash the appropriate code shown

in Table 6. After 15 minutes, with a call for low or high stage

cooling, the compressor contactor is energized. If the thermal

protector has not reset, the outdoor fan is turned off. If the call

for cooling continues, the control will energize the

compressor contactor every 15 minutes. If the thermal

protector closes, (at the next 15 minute interval check), the

unit will resume operation. If the thermal cutout trips for three

consecutive cycles, then unit operation is locked out for 4

hours and the appropriate fault code is displayed.

No 230V at Compressor

If the compressor voltage is not sensed when the

compressor should be starting, the appropriate contactor

may be stuck open or there is a wiring error. The control will

flash the appropriate fault code. Check the contactor and

control box wiring.

Troubleshooting units for proper switching
between low & high stages

Check the suction pressures at the service valves. Suction

pressure should be reduced by 3

10% when switching from

low to high capacity.

NOTE

: The liquid pressures are very similar between low and

high stage operation so liquid pressure should not be used
for troubleshooting.
Compressor current should increase 20

45% when switching

from low to high stage. The compressor solenoid, when

energized in high stage, should measure 24vac across pin

numbers PL5

2 HI and PL5

5 C. When the compressor is

operating in low stage the 24v DC compressor solenoid coil

is de

energized. When the compressor is operating in high

stage, the 24v DC solenoid coil is energized. The solenoid

plug harness that is connected to the compressor has an

internal rectifier that converts the 24v AC signal to 24v DC.

NOTE

DO NOT INSTALL A PLUG WITHOUT AN

INTERNAL RECTIFIER.

Unloader Test Procedure

The unloader is the compressor internal mechanism,

controlled by the DC solenoid, that modulates between high

and low stage. If it is suspected that the unloader is not

working, the following methods may be used to verify

operation.

1. Operate the system and measure compressor

amperage. Cycle the unloader on and off at 30 second

plus intervals at the Wall Control (from low to high

stage and back to low stage). Wait 5 seconds after

staging to high before taking a reading. The

compressor amperage should go up or down at least

20 percent.

2. If step one does not give the expected results, remove

the solenoid plug from the compressor and, with the

unit running and the Wall Control (or Thermostat)

calling for high stage, test the voltage output at the

plug with a DC voltmeter. The reading should be 24

volts DC.

3. If the correct DC voltage is at the control circuit molded

plug, measure the compressor unloader coil

resistance. The resistance should be 330 or 1640

ohms depending on unloader coil supplier. If the coil

resistance is infinite or is grounded, the compressor

must be replaced.

Summary of Contents for CCH6

Page 1: ...hanced installation reliability or operation Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manu...

Page 2: ...d refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing See Fig 1 8 Ensure that tubing insulation is pliable and completely surrounds vapor tube...

Page 3: ...ctions from kit for installation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation To prevent damage to the unit ensure that it is located...

Page 4: ...ft 6 09 m vertical differential refer to Long Line Applications Guideline Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR up to 80 ft 2...

Page 5: ...E HAZARD Failure to follow this caution may result in equipment damage or improper operation Service valves must be wrapped in a heat sinking material such as a wet cloth while brazing CAUTION UNIT DA...

Page 6: ...d Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING ELECTRICAL SHOCK HAZARD Failure to fol...

Page 7: ...ment size See Observer Wall Control Installation Instructions and indoor specification sheet for available adjustments Airflow Setup with Non Communicating Furnace or Fan Coil Two stage compressor ope...

Page 8: ...age 1 Heat Stage 3 Heat Cool Stage 2 Fan 24 VAC Hot Dehumidify 24 VAC Comm Humidify RVS Heating Outdoor G O R W1 Y Y2 C Y1 W2 H O Y1 Y2 C W1 Two Stage Heat Pump Remove J2 Jumper For Heat Staging s s H...

Page 9: ...age of cooling Y1 and O are powered on and with second stage of cooling Y1 Y2 and O are on For these systems with first stage of heating Y1 is on and for second stage of heating Y1 and Y2 are on When...

Page 10: ...There is no delay between staging from low to high and from high to low capacity The compressor will change from low to high and from high to low capacity on the fly to meet the demand DEFROST This c...

Page 11: ...th Accessory Liquid Solenoid Using a Non Communicating Thermostat The liquid solenoid is connected to the Y1 and C terminal connections The liquid solenoid closes in the compressor off mode to prevent...

Page 12: ...te fault code Compressor Thermal Cutout If the control senses the compressor voltage after start up and is then absent for 10 consecutive seconds while cooling demand exists the thermal protector is o...

Page 13: ...ure If the outdoor ambient or coil thermistor should fail the control will flash the appropriate fault code see Table 6 IMPORTANT Outdoor air thermistor and coil thermistor are factory mounted in the...

Page 14: ...INSTALLATION INSTRUCTIONS R 410A Split System Heat Pumps 14 428 01 1703 01 Specifications subject to change without notice Figure 14 Two Stage Control Board...

Page 15: ...ault 55 Coil sensor not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check w...

Page 16: ...10A as with other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig...

Reviews: