Figure 13. Attach the wireless transmitter to the probe
No.
Phenomena
Reason
Solutions
1
The fluid velocity is very
small or zero.
1.1
The probe orientation is wrong
again.
1.2
The connection between probe and
wireless transmitter is not firm
again
1.3
Differential pressure sensor got a
problem or Wireless transmitter got
a problem.
Please consult the manufacturer for
a warranty or replacement.
2
The probe or complete
device vibrates during
operation
2.1
Forget to tighten the screws during
installation
.
3
There is leakage of
Air/Gas nearby the
installation
3.1
The leakage could be from the O-
ring, gasket, or sealing
.
4
From system: HW_Error
= 1
4.1
The lost connection between the
Probe and the wireless transmitter
Check the M12 connector and
tighten it.
4.2
The Probe got a problem.
Please consult the manufacturer for
a warranty or replacement.
There are no moving parts or consumed parts in the AFD Air/Gas Flow Sensor. Therefore there is no need to do
6. Troubleshooting for the AFD Air/Gas Flow
Sensor
7. Maintenance of the AFD Air/Gas Flow Sensor
Summary of Contents for Lidar People Counter
Page 2: ...Daviteq Optical Sensing Technologies...
Page 8: ...Daviteq Radar Sensing Technologies...
Page 9: ...Daviteq Gas Detection Technologies...
Page 27: ......
Page 34: ......
Page 38: ...C m u n i M12 v o c m bi n Si t ch t k t n i M12...
Page 43: ...Daviteq Electrical Sensing Technologies...
Page 51: ...Daviteq Ultrasonic Level Distance Measuring Technologies...
Page 57: ...Thermal mass flow Pitot tube Orifice plate Daviteq Air Gas Flow Measurement Technologies...
Page 64: ...Figure 12 Adjust the orientation of the probe 5 7 Attach the Wireless Transmitter to the probe...
Page 67: ...Daviteq Inertial Measurement Technologies...
Page 80: ...Daviteq Pressure Measurement Technologies...
Page 87: ...Tel 84 28 6268 2523 4 ext 122 Email info daviteq com www daviteq com...