Figure 8. Install the probe into the Nozzle
Figure 9. Fully installed probe on the round pipe
Follow these steps:
Drill a hole of 38mm diameter on the duct surface;
Cleaning the hole;
Place the gasket;
Place the flange;
Screwing the flange to the duct wall by using the self-tapping screws (supplied with the probe)
Insert the probe into the flange neck and tighten the locking screw.
Figure 10. Install the probe into the rectangular duct
Figure 11. The probe is completely installed on the
rectangular duct
Unscrew the locking hex screw M4;
Rotate the probe gently so that the arrow on the probe must be aligned with the pipe/duct direction. The
misalignment must be not higher than 3 degrees;
Tighten the locking screw again.
5.5.2 Install the AFD sensor on the rectangular shape Duct:
5.6 Adjust the orientation of the probe