Instalación del interruptor de flujo
Localice una ubicación adecuada para instalar el interruptor de flujo. El interruptor de flujo debería instalarse
en una sección recta de la tubería con una longitud mínima equivalente a 5 veces el diámetro de la
tubería, a ambos lados del interruptor de flujo, entre este último y cualquier bomba, válvula o piezas. Esto
garantizará que la pala esté expuesta a un flujo no turbulento y tenga una respuesta constante y estable.
FLOW SWITCH INSTALLATION – SCMAX
Locate a suitable position to install the flow switch. The flow switch should be installed on a straight section of pipe
with a minimum of 5 pipe diameters, in either direction, between the flow switch and any pumps, valves, or fittings.
This will ensure that the paddle is exposed to non-turbulent flow and giving a steady and stable response.
The flow switch can be installed in vertical or horizontal pipes, either on the side or on the top of the pipe.
The flow switch should not be mounted on the underside of horizontal pipes.
5 x pipe dia.
minimum.
5 x pipe dia.
minimum.
El interruptor de flujo puede instalarse en tuberías verticales u horizontales, tanto al lado de la tubería como
en la parte superior de esta.
FLOW SWITCH INSTALLATION – SCMAX
Locate a suitable position to install the flow switch. The flow switch should be installed on a straight section of pipe
with a minimum of 5 pipe diameters, in either direction, between the flow switch and any pumps, valves, or fittings.
This will ensure that the paddle is exposed to non-turbulent flow and giving a steady and stable response.
The flow switch can be installed in vertical or horizontal pipes, either on the side or on the top of the pipe.
The flow switch should not be mounted on the underside of horizontal pipes.
5 x pipe dia.
minimum.
5 x pipe dia.
minimum.
El interruptor de flujo no debería montarse en la parte inferior de tuberías horizontales.
FLOW SWITCH INSTALLATION – SCMAX
Locate a suitable position to install the flow switch. The flow switch should be installed on a straight section of pipe
with a minimum of 5 pipe diameters, in either direction, between the flow switch and any pumps, valves, or fittings.
This will ensure that the paddle is exposed to non-turbulent flow and giving a steady and stable response.
The flow switch can be installed in vertical or horizontal pipes, either on the side or on the top of the pipe.
The flow switch should not be mounted on the underside of horizontal pipes.
5 x pipe dia.
minimum.
5 x pipe dia.
minimum.
ESPAÑOL