7.17. Resetting the default settings
(15. menu item)
Function
In this case
all
the settings are deleted, and the default
factory setting is restored.
Using this function makes sense in that case, when the
settings of the instrument have changed so much, that it is
easier to start the setting-up process from the default
factory setting.
It is not possible to cancel this operation once the command
has been issued.
Sequence of operations
1. Enter the menu by typing the supervisor code.
The way the code should be type in is described in Chapter
7.1. Typing the code in.
You see this on the display:
.
2. Keep stepping by pressing the
▲
button as long as you
see this menu item:
.
3. Enter the menu item by pressing the
ENTER
button.
4. The mnemonic
is shown on the display. The
mnemonic is blinking.
Now you still have the possibility to exit. If you want to exit,
as you do not want to reset the default settings after all,
press the
MENU
button. This takes you out from this menu
item, and you see this:
.
5. If you want to reset the default settings, press the
▲
button to change the „NO” to „YES”.
•
= I do not want to reset the default settings
•
= I want to reset the default settings
6. Press the
MENU
button.
The instrument displays the mnemonic
(busy), then
the mnemonic
(ready). After then it restarts:
,
.
According to the factory settings, it measures the loop
current with a resolution of three decimals.
Summary of Contents for DT9502
Page 1: ...DT9502 Intrinsically Safe Temperature Meter Transmitter Operating Instructions ...
Page 64: ...DT9502 64 20171205 V3 10 2 Application example ...
Page 84: ...DT9502 84 20171205 V3 10 9 ATEX Certification ...
Page 85: ...DT9502 20171205 V3 85 ...
Page 86: ...DT9502 86 20171205 V3 ...
Page 87: ...DT9502 20171205 V3 87 ...
Page 88: ...DT9502 88 20171205 V3 ...
Page 89: ...DT9502 20171205 V3 89 ...
Page 90: ...DT9502 90 20171205 V3 ...
Page 91: ...DT9502 20171205 V3 91 ...
Page 92: ......