Installation
This section provides information on:
Operating environment
Rack, wall, & tabletop installation
Connecting sensors
Parts Required
Phillips
9 pin F/F null
Dumb terminal or PC
Screwdriver
modem cable
w/9 pin com port
Operating Environment
Before you install the D-100 Host be sure that your operating environment meets the physical
requirements of the equipment.
Operating Temperature: 32º – 122º Fahrenheit (0º – 50º C)
Humidity:
5 – 90 %RH, non-condensing
Power:
90–260VAC 47/63 Hz outlet within 6'
Rack Requirements:
Standard 19' equipment rack with supplied mounting bracket
hardware. Requires 1.0 EIA rack mount space.
Tabletop requirements:
Flat area which can support an enclosure 17" wide by 10" deep by 2"
high.
Rack Mount Installation
The D-100 Host can be rack mounted using the included rack mount brackets. Follow the steps
below:
1) Attach the unit to the equipment rack using two pan-head screws per side. Tighten the
screws with a Phillips screwdriver.
2) Plug the power cord into a 90-260VAC outlet.
Figure 3: Rack-mounted Host Unit
IMS
S
O
L U T I O
N
SERIAL
ETHERNET
PHONE
E n v i r o n m e n t a l S e n s o r I n p u t s
1
2
3
4
5
6
7
8
MIC
BAT
AC
POWER
ALARM
IMS-4000
1
2
3
4
5
6
7
8
Infrastructure Monitoring System
SENSAPHONE
®
Host
Installation
15
Summary of Contents for D-100 Series
Page 1: ...Installation Manual for Host Node Units Version 1 2 DATAS TECHNOLOGY LTD i...
Page 6: ...Installation Manual vi...
Page 9: ...IMS 4000 Host Installation...
Page 24: ...Installation Manual 24...
Page 26: ...Installation Manual 26...
Page 27: ...4000 Node Installation 27 Node...
Page 38: ...Installation Manual 38...
Page 40: ...Installation Manual 40...