11
See
Troubleshooting
for more explanation of the % Offset displayed after the Light SET method.
13
2.
SET
Sensing
Condition
Method
Action
Result
SET Button
•
Present sensing condition
•
Click the SET Navigation key
Threshold Condition Accepted
Displays read "
Lt SEt
" then alternate
"
PASS
" with % Offset
13
; Sensor
returns to Adjust mode
Threshold Condition Not Accepted
Displays read "
Lt SEt
" then alternate
"
FAIL
" with minimum % Offset
13
for
sensing condition; Sensor returns to
Adjust mode
Remote Input
•
Present sensing condition
T
•
Single-pulse the remote input
3.
Return to RUN Mode
Method
Action
Result
SET Button
Move Mode switch to RUN
Display: Red - Signal Level;
Green - Threshold
Remote Input
No action required; sensor returns to RUN
mode automatically
Dark SET
•
Sets a threshold a programmable % offset above the presented condition
•
Any condition lighter than the threshold condition causes the output to change state
•
Threshold can be adjusted using "+" and "-" Navigation key (Manual Adjust)
•
Recommended for applications where only one condition is known, for example a stable dark background with varying lighter
targets
•
See
Program Mode
for programming the Offset Percent setting
A single sensing condition is presented, and the sensor positions a threshold a programmable % offset above the presented condition.
When a condition lighter than the threshold is sensed, the output either turns ON or OFF, depending on the LO/DO switch setting
(see
LO/DO Switch
in
Top Panel Interface
).
Threshold position
adjusted by
Manual Adjust
Sensor positions
threshold a programmable
% offset above the
presented condition
Output OFF
Output ON
Darkest
(no signal)
Condition
Presented
Most Light
(saturated
signal)
NOTE:
Offset Percent MUST be programmed to
Minimum Offset
to accept conditions of no signal (0 counts).
Figure 7. Dark SET (Light Operate shown)