AMT58x-CB CANopen®
24
1801 PDO2 parameters
PDO2 message is used by default for synchronous transmission of
the position value.
01 COB-ID of the PDO2 [Unsigned32, rw]
If the node address is set using the internal dip-switches (i.e. at
least one dip-switch for setting the node has HIGH logic level = 1),
when the power is turned on, this object is always forced to the
default value. Otherwise, if the node address is set via software
(i.e. all dip-switches for setting the node have LOW logic level = 0)
it retains the set value, unless a software procedure for setting a
new address is forced at power on.
Default = 4000 0280h+NodeID (no RTR, COB-ID)
02 Transmission type [Unsigned8, rw]
Default = 01h(synchronous transmission at each SYNC
command)
Position value is transmitted after a set number of SYNC
commands.
Interval in SYNC commands must be set in object
1801 PDO2
parameters
, sub 2.
1802 PDO3 parameters
PDO3 message is used by default for synchronous transmission of
the position value.
01 COB-ID of the PDO3 [Unsigned32, rw]
If the node address is set using the internal dip-switches (i.e. at
least one dip-switch for setting the node has HIGH logic level = 1),
when the power is turned on, this object is always forced to the
default value. Otherwise, if the node address is set via software
(i.e. all dip-switches for setting the node have LOW logic level = 0)
it retains the set value, unless a software procedure for setting a
new address is forced at power on.
Default = C000 0380h+NodeID (disable, no RTR)
02 Transmission type [Unsigned8, rw]
Default = 01h (synchronous transmission at each SYNC
command).
Position value is transmitted after a set number of SYNC
commands.
Interval in SYNC commands must be set in object
1802 PDO3
parameters
, sub 2.
1803 PDO4 parameters
PDO4 is used by default for cyclic transmission of the velocity value.
See object
6200-00 Cyclic time
for setting the cyclic timer.
01 COB-ID of PDO4 [Unsigned32, rw]
If the node address is set using the internal dip-switches (i.e. at
least one dip-switch for setting the node has HIGH logic level = 1),
when the power is turned on, this object is always forced to the