AMT58x-CB CANopen®
29
6.8.3 Device profile objects (DS 406)
6000-00 Operating parameters
[Unsigned16, rw]
Bit
Function
bit = 0
bit = 1
0
Code sequence
CW
(clockwise)
CCW
(counter
clockwise)
1 not
used
2
Scaling function
disabled enabled
3…11 not
used
12
Limit switch min.
disabled enabled
13
Limit switch max.
disabled enabled
14…15 not
used
Default = 0000h
Code sequence
It defines whether the position value output by the transducer
increases when the encoder shaft rotates clockwise (CW) or
counterclockwise (CCW). When
Code sequence
= 0, the position
value increases when the encoder shaft rotates clockwise; on the
contrary, when
Code sequence
= 1, the position value increases
when the encoder shaft rotates counterclockwise. CW and CCW
rotations are viewed from shaft end.
Scaling function
If disabled the device uses its own physical resolution (see objects
6501-00 Hardware counts per revolution
and
6502-00 Hardware
number of turns
); if enabled it uses the resolution set in objects
6001-
00 Counts per revolution
and
6002-00 Total resolution
with the
following relation:
Transmitted position =
6001-00 Counts per revolution
real position
6002-00
Total resolution
6501-00 Hardware counts per
revolution
WARNING
Every time you enable the scaling function and/or change the scaling
values (see objects
6001-00 Counts per revolution
and
6002-00 Total
resolution
) then you are required to set a new preset value (see
object
6003-00 Preset value
) and finally save the new parameters
(see object
1010-01 Store parameters
).