DKG-519 User Manual V-27
(14.04.2011)
- 40 -
Program Group: Engine Parameters (continued)
Parameter Definition,
(Password Level)
Unit Factory
Set
Description
(2)
2
nd
Low Frequency
Shutdown
Hz
40
When secondary volt/freq limits are active:
If the genset frequency goes under this limit, a
GENSET LOW SPEED
alarm is generated and the
engine stops.
(1)
2
nd
Low Frequency
Warning
Hz
45
When secondary volt/freq limits are active:
If the genset frequency goes under this limit, a
GENSET LOW SPEED
warning is generated.
(1)
2
nd
High Frequency
Warning
Hz
65
When secondary volt/freq limits are active:
If the genset frequency goes over this limit, a
GENSET
HIGH SPEED
warning is generated.
(2)
2
nd
High Frequency
Shutdown
Hz
69
When secondary volt/freq limits are active:
If the genset frequency goes over this limit, a
GENSET
HIGH SPEED
alarm is generated and the engine
stops.
(2)
2
nd
Low rpm Shutdown
rpm
0
When secondary volt/freq limits are active:
If the engine speed goes under this limit, a
GENSET
LOW SPEED
alarm is generated and the engine stops.
(2)
2
nd
Low rpm Warning
rpm
0
When secondary volt/freq limits are active:
If the engine speed goes under this limit, a
GENSET
LOW SPEED
warning is generated.
(2)
2
nd
High rpm Warning
rpm
0
If the engine speed goes over this limit, a
GENSET
HIGH SPEED
warning is generated.
(2)
2
nd
High rpm Shutdown
rpm
0
When secondary volt/freq limits are active:
If the engine speed goes over this limit, a
GENSET
HIGH SPEED
alarm is generated and the engine
stops.