Program Group: Controller Configuration (continued)
Parameter Definition,
(Password Level)
Unit Factory
Set
Description
(1)
Exercise Day and Time
-
168
This parameter defines the start day and hour of the
exerciser.
Values higher or equal to 168 mean that the
exerciser is off.
The exercise may be selected to start at the
beginning of the any hour of the week. The
parameter value is the hour count of the start time.
Examples:
0 = exercise starts at Monday 00:00
8 = exercise starts at Monday 08:00
24 = exercise starts at Tuesday 00:00
167 = exercise starts at Sunday 23:00
168 = exerciser off
If a daily exercise is selected, then the day
information is don’t care and the exercise will be
performed every day regardless of the day selection.
If the monthly exerciser is selected, then the exercise
will be performed during the first 7 days of each
month at the programmed day and hour.
(1)
Exercise Duration
min
10
This parameter defines the exercise duration and
programmed in 10 minute steps up to 24 hours.
(1)
Exercise Off/On Load
-
0
0:
Exercise at
TEST
mode
1:
Exercise at
LOAD TEST
mode
(1)
Exercise Period
-
1
0:
exercise every day (the exercise will be performed
every day regardless of the day selection of Exercise
Dat and Time parameter).
1:
exercise once per week
2:
exercise once per month (the exercise will be
performed during the first 7 days of each month at
the programmed day and hour).
(2)
Delayed Simulate Mains
-
0
0:
The
SPARE-2
input has normal function
1:
The
SPARE-2
input has delayed simulate mains
function. See chapter 6.8 for more info.
(2)
Modem Enable
-
0
0:
No modem connection, the serial port is connected
to PC
1:
Modem connected.
(2)
SMS Enable
-
0
0:
SMS not enabled
1:
SMS enabled
(2)
GPRS Call Enable
-
0
0:
standard modem calls
1:
GPRS modem calls
(2)
MODBUS Address
-
0
0:
RAINBOW communication protocol.
1-144:
MODBUS communication. This parameter is
also the MODBUS controller address of the unit.
(1)
Oil Pressure in psi
-
0
0:
oil pressure display in bars
1:
oil pressure display in psi
(1)
Temperature in °F
-
0
0:
temperature display in degrees C
1:
temperature display in degrees F
(2)
Flashing Relay Timer
hours
0
Delayed Simulate Mains Operation:
max genset
running time after Simulate Mains signal disappears.
Dual Genset Systems:
flashing relay toggle timer.
Please contact DATAKOM for dual genset mutual
stanby operation.