DKG-519 User Manual V-27
(14.04.2011)
- 25 -
6.22. Fuel Theft / Fuelling Messages
The unit is able to send SMS messages in fuel theft or fuelling conditions.
These SMS messages are sent without creating visible fault condition.
These features are enabled by setting the program parameter
Engine Parameters > Fuel
Consumption / Hour
to a value other than 0%.
The
Fuel Consumption / Hour
parameter should be set to a value clearly greater than the
maximum fuel consumption of the engine.
If the fuel level measured from the sender input is decreased more than this parameter in 1
hour period, then a FUEL THEFT sms message is sent to programmed telephone numbers.
If the fuel level measured from the sender input is increased more than this parameter in 1
hour period, then a FUELLING sms message is sent to programmed telephone numbers.
6.23. Firmware Update
The unit offers possibility of updating the firmware in the field. The firmware is updated through
the RS-232 serial port using Rainbow or a special DOS program.
The unit will go to firmware download mode with a special command from the PC program. In
download mode, the display of the unit will show “
DL-V1.00
”
During firmware update process, the progress is visible through a completion bar on the
screen.
The firmware update operation will take around 3 minutes.
After completion of the update a special command will set back the unit to normal operation
mode.
6.24. Engine Control Mode
In engine control mode, the unit is supposed to control an engine without alternator.
The engine control mode is activated by a program parameter in the
Controller
Configuration
group.
When the
Engine Control Mode
is activated:
-the unit will not display genset AC parameters (volts, amps, kW and pf).
-genset voltage and frequency protections are disabled. However engine rpm protections will
be active.
It is strongly recommended to enter correct low and high rpm limit values in order
to enable engine speed protection.