DKG-325 User Manual Firmware V-56
- 14 -
The Charge terminal is both an input and output.
When the engine is ready to run, this terminal supplies the excitation current to the charge alternator.
The excitation circuit is equivalent to a 2W lamp.
Structure:
battery voltage output through 82 ohm resistor
voltage measurement input
Output current:
130mA @12VDC
Charge Fail Warning
Threshold:
6VDC
Open circuit voltage:
battery positive
Overvoltage protection:
> 500VDC continuous, with respect to battery negative
Reverse voltage
protection:
-30VDC with respect to battery negative
Structure:
Genset or mains voltage through 2 internal relays. Internal current
transformers on the load line.
Max. switching current:
25A @250VAC
Max switching voltage:
440VAC
The unit has 3 digital outputs. One of them may be selected as FUEL or STOP. The auxiliary output
function may be selected from list.
Structure:
Positive switching relay outputs
Max. Continuous current:
Fuel & crank:40A, Auxiliary:10A
Max. Switching current:
16 VDC
3.7. DIGITAL OUTPUTS
3.6. LOAD OUTPUTS
3.5. CHARGE INPUT TERMINAL