DKG-325 User Manual Firmware V-56
- 31 -
Oil Pressure Sender Characteristics
PGM
Parameter Definition
Unit Factory Set Description
P_53
Oil Pressure Sender Ohms -1 ohm
10
Oil Pressure Sender point 1, ohm value
P_54
Oil Pressure Value -1
bar
0.0
Oil Pressure Sender point 1, bar value
P_55
Oil Pressure Sender Ohms -2 ohm
52
Oil Pressure Sender point 2, ohm value
P_56
Oil Pressure Value -2
bar
2.0
Oil Pressure Sender point 2, bar value
P_57
Oil Pressure Sender Ohms -3 ohm
90
Oil Pressure Sender point 3, ohm value
P_58
Oil Pressure Value -3
bar
4.0
Oil Pressure Sender point 3, bar value
P_59
Oil Pressure Sender Ohms -4 ohm
140
Oil Pressure Sender point 4, ohm value
P_60
Oil Pressure Value -4
bar
7.0
Oil Pressure Sender point 4, bar value
P_61
Oil Pressure Sender Ohms -5 ohm
156
Oil Pressure Sender point 5, ohm value
P_62
Oil Pressure Value -5
bar
8.0
Oil Pressure Sender point 5, bar value
P_63
Oil Pressure Sender Ohms -6 ohm
184
Oil Pressure Sender point 6, ohm value
P_64
Oil Pressure Value -6
bar
10.0
Oil Pressure Sender point 6, bar value
Coolant Temperature Sender Characteristics
PGM
Parameter Definition
Unit Factory Set Description
P_65
Temperature Sender Ohms -1 ohm
38
Temperature Sender point 1, ohm value
P_66
Temperature Value -1
°C
100
Temperature Sender point 1, °C value
P_67
Temperature Sender Ohms -2 ohm
51
Temperature Sender point 2, ohm value
P_68
Temperature Value -2
°C
90
Temperature Sender point 2, °C value
P_69
Temperature Sender Ohms -3 ohm
134
Temperature Sender point 3, ohm value
P_70
Temperature Value -3
°C
60
Temperature Sender point 3, °C value
P_71
Temperature Sender Ohms -4 ohm
322
Temperature Sender point 4, ohm value
P_72
Temperature Value -4
°C
39
Temperature Sender point 4, °C value
P_73
Temperature Sender Ohms -5 ohm
650
Temperature Sender point 5, ohm value
P_74
Temperature Value -5
°C
20
Temperature Sender point 5, °C value
P_75
Temperature Sender Ohms -6 ohm
978
Temperature Sender point 6, ohm value
P_76
Temperature Value -6
°C
14
Temperature Sender point 6, °C value
Spare Input Input Configuration
PGM
Parameter Definition Unit Fac.Set Description
P_77
Action
0
0:
Shutdown (the engine stops immediately)
1:
Load Dump (the engine stops after cooldown)
2:
Warning (the horn relay operates)
3:
No operation
P_78
Sampling
0
0:
Always
1:
After holdoff timer
2:
When mains present
P_79
Latching
0
0:
Non latching
1:
Latching
P_80
Contact type
0
0:
Normally open
1:
Normally closed
P_81
Switching
0
0:
Battery negative
1:
Battery positive
P_82
Response delay
0
0:
No delay
1:
Delayed (4sec)