DKG-317 MANUAL AND REMOTE START UNIT

 

 
 

 

 

FEATURES 

 

Manual starting and stopping 
Engine control 
Generator protection 
Built in alarms and warnings 
3 phase genset voltage inputs 
3 phase genset CT inputs 
Engine oil pressure measurement 
Engine coolant temperature measurement 
Genset active power measurement 
Genset power factor measurement 
Periodic maintenance request indicator 
Engine hours counter 
Event logging 
Statistical counters 
Field adjustable parameters 
RS-232 serial port 
 

 
Free MS-Windows Remote monitoring SW: 
    -local, LAN,  IP and modem connection 
    -monitoring, download of parameters 
LED displays 
Configurable analogue inputs: 2 
Configurable digital inputs: 7 
Configurable relay outputs: 2 
Total relay outputs: 4 
I/O expansion capability 
Remote Start operation available 
Survives cranking dropouts 
Sealed front panel 
Plug-in connection system for easy replacement 
Small dimensions (165x125x48mm) 
Low cost 

 

Summary of Contents for DKG-317

Page 1: ...wer measurement Genset power factor measurement Periodic maintenance request indicator Engine hours counter Event logging Statistical counters Field adjustable parameters RS 232 serial port Free MS Wi...

Page 2: ...s 3 2 Digital Display 4 ALARMS AND WARNINGS 5 MODES OF OPERATION 6 OTHER FEATURES 6 1 Remote start operation 6 2 Sender type selection 6 3 Service Request Display 6 4 Engine Hour Meter 6 5 Modem conne...

Page 3: ...the retaining steel spring and connectors from the unit then pass the unit through the mounting opening The unit will be maintained in its position by the steel spring Engine body must be grounded fo...

Page 4: ...porate appropriate short circuit backup protection e g a fuse or circuit breaker of High Breaking Capacity HBC at least 1500A 6 Use cables of adequate current carrying capacity at least 0 75mm 2 and t...

Page 5: ...table from a list 19 START RELAY Output 10A 28VDC This relay controls the engine cranking 20 FUEL RELAY Output 10A 28VDC This relay is used for fuel solenoid control It is internally connected to term...

Page 6: ...hours or time duration after previous service has elapsed ALARM GROUP Red If a fault condition resulting to the engine shutdown has occurred the related alarm led turns on steadily If a warning condi...

Page 7: ...generator phase to neutral voltages UV VW WU generator phase to phase voltages If the service counters group is displayed then this display will show the counter name In programming mode it displays P...

Page 8: ...med HIGH TEMPERATURE Set if a signal is detected at the High Temperature Switch input or the coolant temperature value measured from the sender is above the programmed limit Warning P_017 and alarm P_...

Page 9: ...ter P_042 is set to 1 then the unit will enter to the Remote Start operation In this mode the engine will run and stop with the Remote Start signal It is also necessary to set the program parameter P_...

Page 10: ...ing engine hours and the remaining time limit are kept stored in a non volatile memory and are not modified by power supply failures The remaining time and engine hours to service may be checked via t...

Page 11: ...0 CASECOM USB TO SERIAL CONVERTER MODEL RS 01 7 EVENT LOGGING The unit keeps records of the last 12 events in order to supply information for the service personal The events are stored in a circular m...

Page 12: ...er failures To exit the program mode press one of the mode selection keys If no button is pressed during 1 minute the program mode will be cancelled automatically Pgm Definition Unit Std Val Descripti...

Page 13: ...High Battery Voltage Alarm V 33 0 If the battery voltage goes over this limit this will generate a BATTERY alarm and the engine will stop 15 Low Oil Pressure Warning Bar 1 5 If the oil pressure measu...

Page 14: ...limits P_008 P_011 and SPEED FAULT alarm occurs 25 Not used 26 Preheat timer sec 1 This is the time after the fuel solenoid is energized and before the genset is started During this period the PREHEA...

Page 15: ...ngine Hours hours 200 The SERVICE REQUEST led indicator will turn on after this quantity of engine hours from the last service If the period is set to 0 no SERVICE REQUEST will be generated depending...

Page 16: ...n 22 74 RELAY 10 function 23 75 RELAY 11 function 24 76 RELAY 12 function 25 77 RELAY 13 function 26 78 RELAY 14 function 27 79 RELAY 15 function 28 80 RELAY 16 function 29 81 RELAY 17 function 30 82...

Page 17: ...e 1 Battery positive 88 Response delay 0 0 No delay 1 Delayed 4sec HIGH TEMPERATURE SWITCH INPUT Pgm Description Std 89 Operation 0 0 Alarm the engine stops and horn relay operates 2 Warning the horn...

Page 18: ...relay operates 2 Warning the horn relay operates 3 No operation 108 Fault monitoring 0 0 Always 1 After holdoff timer 2 When mains present 109 Latching 0 0 Non latching 1 Latching 110 Contact type 0 0...

Page 19: ...t type 0 0 Normally open 1 Normally closed 129 Switching 0 0 Battery negative 1 Battery positive 130 Response delay 0 0 No delay 1 Delayed 4sec Parameters from P_131 to P_142 define the ohm bar charac...

Page 20: ...red as 0 An example table is given below The sensor characteristics used in this table are 38 C 342 ohms 82 C 71 ohms 104 C 40 ohms 121 C 30 ohms Pgm Description Unit Value 143 Point_1 resistor ohm 30...

Page 21: ...the Amp readings are correct Current transformers are not connected to the correct inputs or some of the CTs are connected with reverse polarity Determine the correct connections of each individual C...

Page 22: ...between BATTERY and charging alternator D terminal The normally closed contact of the relay will be connected serially to the unit s START output So the starting will also be removed when the D pulls...

Page 23: ...Internally connected to battery positive via 4700 ohm resistor Analog inputs Resistor input 0 to 5000 ohms connected to the battery negative Sources 10 mA when closed to battery negative Measurement...

Page 24: ...DKG 317 User Manual V 01 19 01 10 2009 24 14 CONNECTION DIAGRAM...