- 76 -
Parameter
Definition
Unit
Min
Max
Factory
Setting
Description
Fan PID Derivative
(D) coefficient
%
0
99.9
5.0
Fan PID control D coefficient.
Fan PID Correction
(%) coefficient
%
0
99.9
1.0
Fan PID control inverse I coefficient.
Fan PID Delay Timer
Sec
1
99.9
0
Refer to section 25.9 for detailed
information.
Max Number of
Slaves Under Load
-
0
32
0
The function of this parameter is explained
in section 25.11.
Reset All Service
Counters
-
0
1
-
0:
No effect
1:
Resets all service counters. The service
counters are set equal to the relevant
Service Hours parameters. This parameter
is not saved to memory, it is always read as
0.
Reset Service A
Counter
-
0
1
-
0:
No effect
1:
Service A Counter is set equal to the
Service A Timer
parameter. This
parameter is not saved to memory, it is
always read as 0.
Reset Service B
Counter
-
0
1
-
0:
No effect
1:
Service B Counter is set equal to the
Service B Timer
parameter. This
parameter is not saved to memory, it is
always read as 0.
Reset Service C
Counter
-
0
1
-
0:
No effect
1:
Service C Counter is set equal to the
Service C Timer
parameter. This
parameter is not saved to memory, it is
always read as 0.
Reset Service D
Counter
-
0
1
-
0:
No effect
1:
Service D Counter is set equal to the
Service D Timer
parameter. This
parameter is not saved to memory, it is
always read as 0.
Reset Service E
Counter
-
0
1
-
0:
No effect
1:
Service E Counter is set equal to the
Service E Timer
parameter. This
parameter is not saved to memory, it is
always read as 0.
Reset Running hours
Counter
-
0
1
-
0:
No effect
1:
Resets the Running hours counter. This
parameter is not saved to memory, it is
always read as 0.
Reset Loaded
Running Hours
Counter
-
0
1
-
0:
No effect
1:
Resets the Loaded Running hours
counter. This parameter is not saved to
memory, it is always read as 0.
Reset Number of
Motor Starts Counter
-
0
1
-
0:
No effect
1:
Resets the number of motor starts
counter. This parameter is not saved to
memory, it is always read as 0.
Reset Number of Fan
Starts Counter
-
0
1
-
0:
No effect
1:
Resets the number of fan starts counter.
This parameter is not saved to memory, it
is always read as 0.
15.3. COMPRESSOR PARAMETERS GROUP (cont.)