- 59 -
To perform a factory reset:
-Press and hold the
STOP, LAMP TEST
and
ALARM MUTE
buttons for 5 seconds,
-The screen will display
“
FACTORY RESET
”,
-Press the
RIGHT ARROW
key and hold for 5 seconds,
-Factory parameters will be reprogrammed to memory.
The programming mode is used to configure timers, operation limits and program parameters.
All program parameters can be modified from the front panel as well as from the free Rainbow Plus PC
software.
Any changes made to parameters are automatically saved to the nonvolatile memory and are effective
immediately.
Entering the programming mode does not affect device operation.
To enter the programming mode
, press together the
and
buttons for 5 seconds.
The following password prompt will be displayed upon entering programming mode.
buttons are used to enter the 4-digit password.
,
buttons change the digit values.
buttons change the cursor location on the digits.
The unit stores 3 levels of passwords. Level_1 password can be used to make parameters changes
necessary on the field. Level_2 password is used to change settings which need to be made in the
factory. Level_3 password protects the calibration parameters of the unit.
Level-1 password is
‘
1234
’ and level-2 password is ‘
9876
’.
If the password is mistyped, the program parameters can be viewed but cannot be changed.
14.1. RESETTING TO FACTORY DEFAULTS
14.2. ENTERING THE PROGRAMMING MODE
14. PROGRAMMING