- 68 -
Parameter Definition
Unit
Min
Max
Factory
Setting
Description
Temperature Sender for
Heating Relay
-
0
4
0
This parameter selects the sender to be
used to control the heating relay.
0: Temperature Sender-1 (T1)
1: Temperature Sender-2 (T2)
2: Temperature Sender-3 (T3)
3: Temperature Sender-4 (T4)
4: PT100 Temperature Sender (T5)
Heater ON Temperature
°C
-100
100
0
If the measurement sent by the
Temperature Sender for Heating
Relay
parameter is less than
Heater
ON Temperature
, the heating relay
activates. If the measurement is greater
than (
Heater ON Tempe
Heater OFF Temperature Difference
),
the heating relay disengages.
Heater OFF
Temperature Difference
°C
1
30
5
0-10V Analog Output
Configuration
-
0
25
0
This parameter defines the mode of
operation for the 0-10V Analog output.
0: Motor Drive
1: Fan Drive
2: Total Active Power
3: Total Reactive Power
4: Total Power
5: Average Voltage
6: Average Current
7: Average Power Factor (PF)
8: L1 Active Power
9: L2 Active Power
10: L3 Active Power
11: L1 Reactive Power
12: L2 Reactive Power
13: L3 Reactive Power
14: L1 Total
15: L2 Total
16: L3 Total
17: L1-N Voltage
18: L2-N Voltage
19: L3-N Voltage
20: L1-2 Voltage
21: L2-3 Voltage
22: L3-1 Voltage
23: L1 Current
24: L2 Current
25: L3 Current
26: Temperature-1 (T1)
27: Temperature-2 (T2)
28: Temperature-3 (T3)
29: Temperature-4 (T4)
30: Pressure-1 (P1)
31: Pressure-2 (P2)
32: Pressure-3 (P3)
33: PT100 Temperature (T5)
15.2. ELECTRICAL PARAMETERS GROUP (cont.)