- 63 -
Parameter Definition
Unit
Min
Max
Factory
Setting
Description
Web Server Port
-
80
65535
80
Port number of the internal Web server.
The unit responds to incoming queries
to this port only.
Modbus over TCP/IP
Port
-
0
65535
502
Port number of the Internal Modbus
TCP/IP server. The unit responds to
incoming Modbus queries to this port
only.
E-mail Server Port
-
0
65535
587
Server port for e-mail sending.
Modbus Address
-
0
254
1
This parameter is the Modbus address
of the unit.
RS-485 Baud Rate
bps
2400
115200
9600
RS-485 Modbus port communication
speed.
Ethernet Active
-
0
1
1
0:
Ethernet port OFF
1:
Ethernet port ON
Flashing Relay ACTIVE
Timer
Sec
0
6500
0
Flashing relay ACTIVE duration.
Flashing Relay
INACTIVE Timer
Sec
0
6500
0
Flashing relay INACTIVE duration
Real Time Clock
Adjustment
-
0
255
117
This parameter trims precisely the real
time clock circuit. Values from 0 to 63
speed up the clock by 0.25sec/day
steps. Values between 127 and 64 slow
down the clock by 0.25sec/day steps.
CANBus Address
-
1
64
64
This parameter is the CANbus address
for multiple operation. If the address of
any device is set to 32 or lower, this
compressor is included in the multiple
operation network. Refer to section
25.11 for further information on multiple
operation. It is recommended to set the
address to a value between 33-64 if
multiple operation is not performed.
CANBus Communication
Rate
kbps
50
500
250
CANbus communication rate for
multiple operation.
E-mail on IP change
-
0
1
0
If the IP changes when GPRS
connection is established, an e-mail is
sent. No warnings will be shown on the
controller if the IP changes.
0:
No e-mail on IP change.
1:
E-mail sent on IP change.
Remote Control Enabled
-
0
1
1
This parameter enables the remote
control of the controller via Rainbow,
Modbus, and Modbus TCP/IP.
0:
Remote control disabled
1:
Remote control enabled
Log Records Period
Sec
5
3600
5
This parameter adjusts the data logging
frequency to micro-SD or USB Flash
memories. Frequent recording will
require higher memory capacity. With a
period of 2 seconds, 4GB per year of
memory is necessary. With a period of
1 minute, 133MB is consumed per year.
LCD Backlight Timer
Min
0
1440
60
If no button is pressed during this
period, the unit will reduce the LCD
screen backlight intensity for economy.
15.1. CONTROLLER CONFIGURATION GROUP (cont.)