- 34 -
Term Function
Technical data
Description
1
SUP+
85-300V-AC or
88-400V-DC
Connect the PHASE terminal of the AC
supply to this terminal. If DC supply is
used, connect the (+) terminal.
Reverse connection does not affect device
operation.
2
-
-
No connection
3
SUP-
Neutral or 0 VDC
Connect the NEUTRAL terminal of the AC
supply to this terminal. If DC supply is
used, connect the (-) terminal.
Reverse connection does not affect device
operation.
Term Function
Technical data
Description
4
PT100 Sender Input
75-240 ohm
resistance measuring
circuit
If PT100 sender is used, it must be
connected between this terminal and the
adjacent SGND terminal.
5
SGND (sender ground)
0 VDC
One terminal of the PT100 and other
temperature senders must be connected
here.
6
0-10V Analog Output
DC 0-10 V
Output resistance 1 k-
ohm
This output supplies 0-10VDC analog
voltage in order to control the frequency
inverter. The output is controlled by a PID
loop.
7
PRES+ (12V Pressure
sender Supply)
DC +12V output
70mA max.
The output supplies the positive to the 4-
20mA pressure senders.
8
Pressure Sender-3 Input
4-20mA inputs
The (-) terminal of the 4-20mA output
pressure senders is connected to this
terminal. The (+) terminal of the senders
must be connected to the PRES+ terminal.
9
Pressure Sender-2 Input
10
Pressure Sender-1 Input
11
Analog Temperature
Sender-1
1 k-ohm
– 100 k-ohm
resistance measuring
inputs
One terminal of the NTC/PTC type
temperature senders must be connected
to this terminal. The other terminal of the
senders must be connected to SGND.
12
Analog Temperature
Sender-2
13
Analog Temperature
Sender-3
14
Analog Temperature
Sender-4
Term Function
Technical data
Description
15
4-20mA Output-1+
Externally supplied,
passive and isolated
4-20mA analog
outputs.
These outputs are designed to transfer
information to external PLC systems. Any
analog measurement can be programmed
to the desired output.
16
4-20mA Output-1-
17
4-20mA Output-2+
18
4-20mA Output-2-