background image

 

 

 

 

DK-70 

INTERNET BASED 

COMPRESSOR 

CONTROLLER 

 

 

DK-70 is a next generation compressor controller 
providing control of a screw or piston type air compressor 
driven by electric motor.   

DK-70 offers wide internet-based communication 
capabilities satisfying tomorrow

’s needs. It allows remote 

monitoring and control over internet. A mobile phone app 
is also available for ease of use. 

The unit incorporates all functions needed in a 
compressor control panel, eliminating the need for extra 
modules in the panel and lowering panel cost.   

The early start function analyzes the air consumption 
trend and starts the compressor before the pressure falls 
below the low set limit. 

Using the Weekly Schedule Program and Pressure 
Calendar functions, the compressor can be programmed 
to start on given hours and days of the week with user 
defined set pressure values. 

The unit is supplied from the utility. Fault contacts and 
senders are internally supplied, eliminating the need for a 
supply transformer in the panel. 

The 

2.9”, 128x64 pixel LCD screen displays values in 

bigger size with graphic support. 

The controller is designed to conform to highest industrial 
standards in safety, vibration, EMC and environmental 
conditions.  

Firmware updates can be done easily via the USB port.  

The device can be monitored and programmed via USB, 
RS-485, Ethernet, WIFI and GPRS using the Windows 
based free PC software. 

Rainbow Scada web service enables central remote 
monitoring and control of an unlimited number of 
compressors. 

 

           

          

 

 

Ethernet (optional)  

GSM-2G-3G-4G-NB/IOT-SMS (optional)  

Wi-Fi connection (optional) 
Embedded Web server 
Monitoring & programming & control 
Canbus multi-compressor operation (opt.) 
Modbus RS-485 (optional) 
RS-232 (optional) 
Modbus TCP/IP - SNMP 
USB Flash Drive socket (
optional
USB GPS support 
USB Device Port 
 

 

Equal aging, multiple compressor control 
Weekly schedule and pressure calendar 
5 independent service counters 
Star / Delta starting 
0-10V and 4-20mA frequency inverter control  
8 programmable relay outputs 
8 programmable digital inputs 
3 pressure sender inputs 
4 temperature sender inputs 
Adjustable sender curves 
Current, voltage, power, and phase sequence 
protections 
V & I harmonic analysis and oscilloscope 

Fully closed front panel (IP65 with gasket)

 

 

 

3 phase 4 wire, star 
3 phase 4 wire, delta 
3 phase 3 wire, 2 CTs (L1-L2) 
3 phase 3 wire, 2 CTs (L1-L3) 
2 phase 3 wire, L1-L2 
1 phase 2 wire 
 

FUNCTIONS 

FEATURES 

CONNECTIONS 

DESCRIPTION 

Summary of Contents for DK-70

Page 1: ...gned to conform to highest industrial standards in safety vibration EMC and environmental conditions Firmware updates can be done easily via the USB port The device can be monitored and programmed via...

Page 2: ...ntact Datakom at the e mail address below technical support datakom com tr If additional information to this manual is required please contact the manufacturer directly at technical support datakom co...

Page 3: ...PTION 01 26 03 2019 OK First Edition CAUTION Potential risk of injury or death WARNING Potential risk of malfunction or material damage ATTENTION Useful hints for the understanding of device operation...

Page 4: ...4 Screw type bracket Stock Code J10P01 per unit Self retaining type bracket Stock Code K16P01 per unit Sealing Gasket Stock Code L057P01 SPARE PARTS...

Page 5: ...efore working on the equipment Do not touch the terminals when the controller is connected to the network Short circuit terminals of unused current transformers Any electrical parameter applied to the...

Page 6: ...3 13 ETHERNET PORT OPTIONAL 3 14 USB DEVICE PORT 3 15 USB HOST PORT OPTIONAL 3 16 RS 232 PORT OPTIONAL 3 17 GSM MODEM OPTIONAL 3 18 WIFI COMMUNICATION OPTIONAL 4 TOPOLOGIES 4 1 3 PHASE 4 WIRE STAR 4 2...

Page 7: ...EN MENUS 14 4 MODIFYING PARAMETER VALUE 14 5 EXITING PROGRAMMING MODE 15 PROGRAM PARAMETER LIST 15 1 CONTROLLER CONFIGURATION GROUP 15 2 ELECTRICAL PARAMETERS GROUP 15 3 COMPRESSOR PARAMETERS GROUP 15...

Page 8: ...21 7 VARIABLE UNLOADED OPERATION TIMER 21 8 PID CONTROL AND ANALOG OUTPUT PWM 21 9 PID CONTROLLD FAN DRIVE 21 10 MOTOR PTC INPUT 21 11 MULTIPLE COMPRESSOR OPERATION 22 MODBUS COMMUNICATION 22 1 PARAM...

Page 9: ...oltage at measuring terminals beyond the specified range Voltage at digital inputs beyond the specified range Current through measuring terminals beyond the specified range Overload or short circuit a...

Page 10: ...10 Dimensions 211x162x42mm Panel cutout 176x121mm minimum Weight 500g approx 2 1 DIMENSIONS 2 MOUNTING...

Page 11: ...s parts of the unit other than the front panel Mount the unit on a flat vertical surface Before mounting remove the mounting brackets and connectors from the unit then pass the through the mounting op...

Page 12: ...ferent types of brackets are provided Screw type bracket Self retaining type bracket Installation of screw type bracket Installation of self retaining type bracket Do not tighten too much this may bre...

Page 13: ...0 mm diameter and greater 5 Protected from the amount of dust that would interfere with normal operation 6 Dust tight 2nd Digit Description of Protection Level 0 Not protected 1 Protected against vert...

Page 14: ...ure range Use adequate cable section at least 0 75mm2 AWG18 Follow national rules for electrical installation Current transformers must have 5A or 1A output For current transformer inputs use at least...

Page 15: ...nge 0 300 VAC phase neutral 0 520V phase phase Minimum voltage for frequency detection 15 VAC Ph N Supported topologies 3 phase 4 wire star 3 phase 3 wire delta 3 phase 4 wire delta 2 phase 3 wire L1...

Page 16: ...nge Selecting the CT Rating and Cable Section The load on a CT should be kept to a minimum in order to minimize the phase shift effect of the current transformer Phase shift in a CT will cause erroneo...

Page 17: ...oth the order of the CTs and their polarities Reactive power measurement is affected by incorrect CT connections in a similar way as active power measurement CORRECT CT CONNECTIONS Let s suppose that...

Page 18: ...100 0 0 0 100 1 00 Phase L3 100 0 0 0 100 1 00 Total 100 0 0 0 300 0 33 EFFECT OF PHASE SWAPPING The compressor is still loaded with 100 kW in each phase The load power factor PF is 1 PF in phases L2...

Page 19: ...Wheatstone bridge and instrumentation op amp Measurement Analog resistance measurement Function The measured resistance value is converted to temperature via the preprogrammed PT100 sender curve Analo...

Page 20: ...med sender curve Nominal input current 4 20mA DC Current measurement range 0 30mA DC Breakdown limit 70mA DC Resolution 12 bit Accuracy 0 5 Noise filtering Yes Number of outputs 0 10V analog output St...

Page 21: ...og outputs 2 Structure Passive output with two terminals External supply required Function selection From list upper lower limits are programmable Output current range 3 6 22mA DC Input supply voltage...

Page 22: ...n be programmed from the main controller Any function in the list can be assigned to the desired digital input The number of digital outputs can be increased using the DKG 186 Digital Output FET Expan...

Page 23: ...cable 200m 115200 baud with 120 ohm balanced cable The RS 485 port features MODBUS RTU protocol Multiple modules can be paralleled on the same RS 485 bus for data transfer to automation or building m...

Page 24: ...lation 1500 VAC 1 minute Max distance 30m Function Embedded TCP IP Web Server Web Client SMTP e mail SNMP Modbus TCP_IP STANDARD ETHERNET CABLE LED FUNCTIONS GREEN This LED turns on when Ethernet conn...

Page 25: ...software programming control of the compressors and monitoring of measured parameters are achieved The RainbowPlus software can be downloaded from www datakom com tr The connector on the module is of...

Page 26: ...s The USB host port is designed for detailed data recording The period of recording is adjustable through program parameter As soon as a USB flash memory is inserted the unit will start data recording...

Page 27: ...n 5 wire Rx Tx DTR CxD GND Full duplex Baud rate 2400 115200 baud adjustable Data type 8 bit data no parity 1 bit stop Isolation 250VAC 1 minute Max distance 15m Cable type Standard modem cable Connec...

Page 28: ...t SMTP Modbus TCP IP client SMS e mail Operating temp range 40 C 85 C Data rate max 85 6 kbps download 42 8 kbps upload SIM card type External SIM 3V 1 8V GPRS active Antenna 4 band magnetic with 2m c...

Page 29: ...Wi Fi protocols 802 11 b g n Frequency range 2 4 GHz 2 5 GHz 2400M 2483 5M Network Protocols IPv4 TCP UDP Security WPA WPA2 Functionality Web Client E mail Modbus TCP_IP 3 18 Wi Fi COMMUNICATION OPTIO...

Page 30: ...30 Various topologies can be selected from the program parameters 4 2 3 PHASE 4 WIRE DELTA 4 1 3 PHASE 4 WIRE STAR 4 TOPOLOGIES...

Page 31: ...31 4 4 3 PHASE 3 WIRE DELTA 2 CT L1 L3 4 3 3 PHASE 3 WIRE DELTA 2 CT L1 L2...

Page 32: ...32 4 6 1 PHASE 2 WIRE 4 5 2 PHASE 3 WIRE DELTA 2 CTs L1 L2...

Page 33: ...33 5 CONNECTION DIAGRAM...

Page 34: ...e frequency inverter The output is controlled by a PID loop 7 PRES 12V Pressure sender Supply DC 12V output 70mA max The output supplies the positive to the 4 20mA pressure senders 8 Pressure Sender 3...

Page 35: ...erm Function Technical data Description 51 Digital Input 1 Digital Inputs 0 150V DC This input is programmable Factory setting User Function 1 52 Digital Input 2 This input is programmable Factory set...

Page 36: ...AL 0 300V AC Neutral terminal for utility mains 67 MAINS L3 Phase Utility mains phase inputs 0 300V AC Connect the utility mains phases to these terminals High and low limits for mains phase voltages...

Page 37: ...bit PT100 Input Measurement range 75 240 ohm Accuracy 12 bit Digital inputs Number of inputs 8 Threshold level 6V DC AC 4 20mA Analog outputs Number of outputs 2 Output range 3 6 22mA Accuracy 16 bit...

Page 38: ...m minimum Weight 500g approx Enclosure High temperature non flammable ROHS compliant ABS PC Mounting Front panel mounted with rear retaining plastic brackets EU Directives Conformity 2014 35 EC Low vo...

Page 39: ...UNCTIONALITY 7 DESCRIPTION OF CONTROLS LINE MAIN relay status indicator i areti Fault status indicators LCD screen Next screen in the same group LAMP TEST if held pressed Previous group screen Next gr...

Page 40: ...UTE long press When held pressed for 5 seconds enters PROGRAMMING mode Reset to factory defaults Please refer to RESETTING TO FACTORY DEFAULTS chapter for more details When held pressed for 5 seconds...

Page 41: ...unters digital output counters demands minimum and maximum values etc Scopemeter Display This group displays waveforms of voltages and currents as an oscilloscope All Ph N and Ph Ph voltages and curre...

Page 42: ...ture parameters P1 Pressure measured by the 1st pressure sender P2 Pressure measured by the 2nd pressure sender P3 Pressure measured by the 3rd pressure sender P12 Difference of the pressures measured...

Page 43: ...occurs this LED turns on SERVICE REQUEST If one of the service counters expires this LED turns on PROGRAMMABLE LEDS The controller offers 2 LEDs which can be user defined Any alarm input or relay func...

Page 44: ...store 100 samples in memory and has 13 bit resolution Sampling rate is 4096Hz This one cycle of a 50Hz signal is represented with 82 points The waveform is displayed on the device screen and on PC scr...

Page 45: ...em all 31 harmonics will be displayed but on a 60Hz system only 29 harmonics will be shown on screen Graphical Harmonic Table Alphanumeric Harmonics Table Harmonics are represented by 2 different meth...

Page 46: ...conds resets the min max values Min max values can also be reset from the programming menu relevant parameter ELECTRICAL PARAMETERS Reset Min Max For more robust results min max detection starts 10 se...

Page 47: ...tarts Alarm bits Digital input and output bits There are various possible event sources Each source can be individually enabled or disabled Program mode entrance event recorded with the password level...

Page 48: ...nt logs will display the next information in the same event will display the previous information in the same event will display the same information of the previous event will display the same inform...

Page 49: ...unning hours Number of motor starts Number of fan starts Minutes left until next oil service request 1st digital input pulse counter 2nd digital input pulse counter Engine hours to Service A Engine ho...

Page 50: ...ses and the motor keeps running for the duration of Safety Timer or Unload Timer whichever is longer If the RUN button is pressed while this timer is counting down the compressor will enter run mode a...

Page 51: ...aches the Stop Pressure or the pressure switch closes the load relay will release and the motor will run off load for the duration of Unload Timer If the output pressure falls below Start Pressure bef...

Page 52: ...y Compressor stops immediately 2 WARNINGS These faults are lower priority warnings ALARM LED flashes The alarms feature low high level settings and timers If the fault cause is removed before the prog...

Page 53: ...y 20 hours The compressor stops Service request warning is given and the service LED turns on The compressor may be run again by pressing the RUN button Between 210 and 300 hours and once every 10 hou...

Page 54: ...se currents is above the High Current Alarm parameter for the duration of Current Alarm Timer Over Current Alarm occurs HIGH VOLTAGE THD If any of the phase voltages THD Total Harmonic Distortion is a...

Page 55: ...ifference and the T13 T1 T3 temperature difference exceeds T1 T3 Temperature Difference Alarm parameter or the T23 T2 T3 temperature difference exceeds T2 T3 Temperature Difference Alarm parameter Sen...

Page 56: ...closed signal from the auxiliary contact is not received within 5 seconds after the main motor contactor closes this alarm occurs MAIN CONTACTOR FAIL TO OPEN If any of the programmable input function...

Page 57: ...Service A Timer Warning Service B Timer Warning Service C Timer Warning Service D Timer Warning Service E Timer Warning To reset the service counters hold pressed and for 5 seconds Completed will be d...

Page 58: ...command and the compressor unloads MODBUS TAKE LOAD COMMAND If the Take Load Command Source parameter is set to 2 Modbus Command this warning is issued when the take load command is sent over Modbus...

Page 59: ...ect device operation To enter the programming mode press together the and buttons for 5 seconds The following password prompt will be displayed upon entering programming mode buttons are used to enter...

Page 60: ...rogram parameters The selected parameter will be marked with an arrow sign next to it Press the button to view change the parameter value The parameter value is incremented decremented with the button...

Page 61: ...rformed the controller will exit programming mode automatically after 2 minutes 14 4 MODIFYING PARAMETER VALUE 14 5 EXITING PROGRAMMING MODE Decrement parameter value Increment parameter value Previou...

Page 62: ...ection 0 5 1 0 no modem no GPS 1 Internal modem no GPS 2 External Datakom modem no GPS 3 External generic modem no GPS 4 No modem RS 232 GPS 5 Internal modem RS 232 GPS GSM SIM Card PIN 0000 9999 0 If...

Page 63: ...ple operation If the address of any device is set to 32 or lower this compressor is included in the multiple operation network Refer to section 25 11 for further information on multiple operation It i...

Page 64: ...ssor Fan Stop Together 0 1 1 0 When the compressor turns off Fan OFF Temperature is checked to turn off the fan 1 The fan turns off with the compressor Local Time Zone Hours 12 12 3 This parameter sel...

Page 65: ...tion of this timer the relevant alarm occurs Voltage Alarm Latching 0 1 0 0 non latching 1 latching Low Frequency Alarm Value Hz 0 400 0 When mains frequency drops below this value an alarm occurs If...

Page 66: ...f Current Alarm Timer Over Current Alarm occurs If this value is set to 0 the alarm is disabled Current Alarm Timer Sec 0 255 30 If any of the phase currents is outside the limits for the duration of...

Page 67: ...4 Wire Star 1 1 Phase 2 Wire 2 2 Phase 3 Wire L1 L2 CT 3 3 Phase 4 Wire Delta 4 3 Phase 3 Wire L1 L2 CT 5 3 Phase 3 Wire L1 L3 CT Minimum Displayed Current 0 100 4 This parameter defines the minimum...

Page 68: ...disengages Heater OFF Temperature Difference C 1 30 5 0 10V Analog Output Configuration 0 25 0 This parameter defines the mode of operation for the 0 10V Analog output 0 Motor Drive 1 Fan Drive 2 Tot...

Page 69: ...value must be set to the measurement value corresponding to 10V 0 10V Analog Output MAX Value 0 3200 0 0 Inverter Minimum Load Speed rpm 0 9900 1800 The minimum rpm for the motor driven by the inverte...

Page 70: ...measurement value exceeds this parameter a warning is displayed Low Temperature 1 Alarm Value C 400 400 0 If the 1st temperature measurement value drops below this parameter an alarm occurs Temperatu...

Page 71: ...s the delay timer for high and low temperature alarms Temperature Sender 2 Offset Value C 20 20 0 This offset parameter is added to the 2nd temperature measurement value Star Duration Sec 2 20 7 This...

Page 72: ...Wait 1 Hour Before Stopping warning is displayed and the motor is not allowed to stop until the hour is up The motor will not stop even if the pressure is sufficient it continues to run off load Fan...

Page 73: ...sor stops as explained in section 13 1 when a service timer expires Variable Service Hours 0 1 0 0 Constant service hours coefficient 1 Variable service hours coefficient Explained in detail in sectio...

Page 74: ...erature Sender 4 Configuration C 0 3 0 0 Disabled 1 Absolute Temperature 2 Temperature Difference 3 Motor PTC MPTC High Temperature alarm occurs when sender measurement value exceeds 2000 Ohms Tempera...

Page 75: ...PT100 temperature measurement will not be displayed and the relevant alarms will be disabled PT100 High Temperature Alarm Value C 400 400 110 If the PT100 temperature measurement value T5 exceeds thi...

Page 76: ...Reset Service C Counter 0 1 0 No effect 1 Service C Counter is set equal to the Service C Timer parameter This parameter is not saved to memory it is always read as 0 Reset Service D Counter 0 1 0 No...

Page 77: ...operation is performed for the compressor The compressor performs load unload cycles until it reaches the Minimum Loading Temperature Pre Heating Offload Timer adjusts the unloaded working duration i...

Page 78: ...the compressor 0 Temperature Sender 1 T1 1 Temperature Sender 2 T2 2 Temperature Sender 3 T3 3 Temperature Sender 4 T4 4 PT100 Temperature Sender T5 Main Pressure Sender 0 2 0 This parameter selects...

Page 79: ...ekly operation schedule and start stop automatically the Weekly Operation Schedule Enabled parameter in the Controller Configuration Group must be set to 1 If the Weekly Operation Schedule Enabled par...

Page 80: ...r s duration is set to 0 it is disabled In order for the compressor to operate according to the Pressure Calendar the Pressure Calendar Enabled parameter in the Controller Configuration Group must be...

Page 81: ...6 ohm value Sender Curve 6 temp C 32768 32767 20 Step 6 temperature value Sender Curve 7 ohm ohm 0 65535 2080 Step 7 ohm value Sender Curve 7 temp C 32768 32767 30 Step 7 temperature value Sender Cur...

Page 82: ...e 7 mA mA 0 512 0 10 0 Step 7 mA value Sender Curve 7 pressure bar 0 3000 0 6 0 Step 7 pressure value Sender Curve 8 mA mA 0 512 0 11 0 Step 8 mA value Sender Curve 8 pressure bar 0 3000 0 7 0 Step 8...

Page 83: ...nder Curve 7 temp C 32768 32767 30 Step 7 temperature value Sender Curve 8 ohm ohm 0 6553 5 115 5 Step 8 ohm value Sender Curve 8 temp C 32768 32767 40 Step 8 temperature value Sender Curve 9 ohm ohm...

Page 84: ...0 3 0 always 1 When motor is running on or off load 2 When motor running on load 3 If load relay is not closed Latching LAT 0 1 0 non latching The fault is dismissed when the alarm cause is removed 1...

Page 85: ...lay 18 133 External output module 2 Factory set Not used Relay 19 133 External output module 2 Factory set Not used Relay 20 133 External output module 2 Factory set Not used Relay 21 133 External out...

Page 86: ...ation 62 Input 14 simulation 63 Input 15 simulation 64 Input 16 simulation 65 User output 1 66 User output 2 67 User output 3 68 User output 4 69 User output 5 70 User output 6 71 User output 7 72 Use...

Page 87: ...ne site ID Engine serial number is used to identify the compressor on which the controller is mounted In the SMS and e mail messages sent by the controller and also on the webpage the engine serial nu...

Page 88: ...he correct APN name SMS Service Center No SMS service number may be required by GSM operators However some operators allow SMS sending without entering a service number Refer to your GMS network provi...

Page 89: ...t Setting documents Membership Address members dyndns org This string is used in Dynamic DNS feature The unit will register itself to the dynamic DNS server under this name For detailed information pl...

Page 90: ...ility of Internet connection at this interval Rainbow Refresh Rate Sec 0 65535 60 The unit will update the remote monitoring terminal at this rate Rainbow Scada Address 1 Port 80 65535 90 This is the...

Page 91: ...SNTP Refresh Rate 30 seconds This is the waiting period between two outbound SNTP requests in order to synchronize its internal RTC with the servers SNTP Address 1 Port 123 This is the port number of...

Page 92: ...ddress are set to 0 0 0 0 then the unit will get the gateway address automatically If you are not an IP professional please leave this address as 0 0 0 0 Subnet Mask 255 255 255 0 Reserved for IP prof...

Page 93: ...d from GSM system APN User Name The APN access point name username may be required by the GSM operator However some GSM operators may allow access without username The exact information should be obta...

Page 94: ...uter IPv4 address If the Network IP address and Gateway IP Address are set to 0 0 0 0 then the unit will get the gateway address automatically If you are not an IP professional please leave this addre...

Page 95: ...ctive state OUT1 OFF Set remote controlled output 1 to passive state OUTxx ON Set remote controlled output xx to active state xx denotes any number between 1 and 16 OUTxx OFF Set remote controlled out...

Page 96: ...memory or a MICRO SD card is inserted the unit will start data recording and continue until the memory is removed USB FLASH DRIVE 20 1 DATA RECORDING MEDIA The USB Host port and MICRO SD card slot are...

Page 97: ...90331 meaning March 31 2019 Thus alphabetical listing will produce a sorted list by date of recording The recorded file type is CSV comma separated values This is a text file which can be opened using...

Page 98: ...der 2 temperature measurement T2 Sender 3 temperature measurement T3 Sender 4 temperature measurement T4 Sender 1 pressure measurement P1 Sender 2 pressure measurement P2 Sender 3 pressure measurement...

Page 99: ...e L1 L2 and L3 phase measurements will not be displayed on screen The controller offers externally controllable digital output functions To enable this feature the digital outputs must be set to one o...

Page 100: ...of the main temperature measurement When the variable coefficient calculation method is active Variable Service Hours parameter is set to 1 On load Up to 90 C the multiplier is 1 Between 90 95 C the...

Page 101: ...he pressure value Pi Restart Pressure at which the motor will restart Pressure Loss Prevention Method 0 None No extra measures taken to prevent pressure loss Pi Start Pressure in all circumstances Pre...

Page 102: ...eeds Motor PID Start Temperature parameter and starts generating the signal after the Motor PID Start delay expires The motor PID control coefficients can be adjusted from Motor PID P coefficient Moto...

Page 103: ...he master device and continuously runs according to Stop Pressure and Start Pressure The other devices in the group run and stop according to their engine hours age 3 If any of the devices become youn...

Page 104: ...lass 10 Supported functions Function 3 read multiple registers Function 6 write single register Function 16 write multiple registers Each register consists of 2bytes 16 bits Larger data structures are...

Page 105: ...ol the IPv4 input to the device Ethernet Network IP Must be left as 0 0 0 0 if the device is required to receive a dynamic IP The desired static IP address must be entered here in order to give the de...

Page 106: ...se L2 apparent power 10280 R 32bit x10 Phase L3 apparent power 10282 R 32bit x10 Total apparent power 10284 R 16bit x1000 Phase L1 power factor 10285 R 16bit x1000 Phase L2 power factor 10286 R 16bit...

Page 107: ...Pressure sender 3 pressure value P3 10459 R 16bit x1 PT100 temperature sender temperature value T5 10460 R 16bit x1 T1 T2 Temperature difference value 10461 R 16bit x1 T1 T3 Temperature difference val...

Page 108: ...o Service E 10603 R 32bit x1 Number of motor starts counter 10605 R 32bit x1 Number of fan starts counter 10607 R 32bit x1 Time left for oiling minutes counter 10609 R 16bit x1 Controller ID number 10...

Page 109: ...oltage 10679 R 32bit x10 Phase L2 L3 Maximum voltage 10681 R 32bit x10 Phase L3 L1 Maximum voltage 10683 R 32bit x10 Phase L1 Maximum current 10685 R 32bit x10 Phase L2 Maximum current 10687 R 32bit x...

Page 110: ...16 status Extension input 8 31 Digital input 32 status Extension input 24 D J TAL OUTPUT R LE DURUM B TLER BIT A IKLAMA BIT A IKLAMA 0 Digital output 4 status 16 Digital output 17 status Extension out...

Page 111: ...rm 48 Motor Overload Alarm 22 Low Temperature Sender 2 Alarm 49 Main Contactor Fail to Close Alarm 23 Sender 2 Temperature Difference Alarm 50 Main Contactor Fail to Open Alarm 24 Temperature Sender 3...

Page 112: ...tive alarm 65 User output 2 110 Press Alarm Sender 1 21 Reactive power alarm 66 User output 3 111 Press Alarm Sender 2 22 Capacitive PF alarm 67 User output 4 112 Press Alarm Sender 3 23 Inductive PF...

Page 113: ...TS BIT DESCRIPTION BIT DESCRIPTION 0 Digital input 1 alarm 4 Digital input 5 alarm 1 Digital input 2 alarm 5 Digital input 6 alarm 2 Digital input 3 alarm 6 Digital input 7 alarm 3 Digital input 4 ala...

Page 114: ...election If the following decimals are entered into this address the corresponding harmonic channel is selected 0 Phase L1 voltage 1 Phase L2 voltage 2 Phase L3 voltage 6 Phase L1 L2 voltage 7 Phase L...

Page 115: ...nter 2 8207 W 16bit x1 The value entered into this address is subtracted from Digital input pulse counter 2 8208 W 16bit x1 The value entered into this address is added to Running hours counter 8209 W...

Page 116: ...orresponding logs can be read 0 Block 0 Event records 1 64 1 Block 1 Event records 65 128 2 Block 2 Event records 129 192 3 Block 3 Event records 193 256 4 Block 4 Event records 257 320 5 Block 5 Even...

Page 117: ...emperature value 11 R 8bit x1 PT100 sender temperature value 12 R 8bit x1 Reserved 13 14 R 32bit x10 Running hours counter 15 16 R 32bit x10 Loaded running hours counter 17 R 16bit x10 Phase L1 voltag...

Page 118: ...cimal R W DATA COEFF DESCRIPTION 5120 R 16bit x1 Year 0 4096 5121 R 16bit x1 Month 1 12 5122 R 16bit x1 Day 1 31 5124 R 16bit x1 Hour 0 23 5125 R 16bit x1 Minute 0 59 5126 R 16bit x1 Second 0 59 22 6...

Page 119: ...I3 Average Minimum Frequency Minimum Active power Minimum Inductive Power Minimum Capacitive Power Max Mains Voltages L1 L2 L3 L12 L23 L31 Maximum Mains Currents I1 I2 I3 Average Maximum Frequency Ma...

Page 120: ...ired static IP address to give a static IP Ethernet Gateway IP Must be set according to your router Ethernet Subnet Mask Must be set according to your router Please refer to Ethernet Configuration Gui...

Page 121: ...electrical and electronic equipment WEEE this unit should be stored and disposed separately from usual waste The unit is compliant to DIRECTIVE 2011 65 EU OF THE EUROPEAN PARLIAMENT AND OF THE COUNCI...

Reviews: