The unit has 3 analog sender inputs. Only parameters of one sender are explained below. Other senders
have identical parameter set.
Each sender has 16 step programmable curves. The sender name and reading unit is freely
programmable, thus the sender can be adapted to any type through programming.
Each sender has below programmable parameters:
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Sender Type
-
0
15
Selects between predefined sender
functions. If this parameter is set to 13-
14-15 then the sender name string can
be freely entered.
Alarm Level
-
0
1
0:
shutdown alarm
1:
loaddump alarm
Alarm Handling
-
0
3
0:
always
1:
on engine running
2:
after hold-off timer
3:
reserved
Sender Open Alarm
-
0
3
If sender resistor is above 5000 ohms,
a fault case is generated. This
parameter defines the action taken
upon fault case.
0:
no alarm
1:
shutdown alarm
2:
loaddump alarm
3:
warning
Low Alarm Check Enable
0
0
1
The low alarm may be selected as
shutdown or loaddump with “alarm
level” parameter.
0:
low value alarm disabled
1:
low value alarm enabled
Low Warning Check
Enable
0
0
1
0:
low value warning disabled
1:
low value warning enabled
High Alarm Check
Enable
0
0
1
The high alarm may be selected as
shutdown or loaddump with “alarm
level” parameter.
0:
high value alarm disabled
1:
high value alarm enabled
High Warning Check
Enable
0
0
1
0:
high value warning disabled
1:
high value warning enabled
Low Alarm Level
x
0
10000
If enabled, defines the low alarm limit.
The low alarm may be selected as
shutdown or loaddump with “alarm
level” parameter.
Low Warning Level
x
0
10000
If defined, defines the low warning.
High Alarm Level
x
0
10000
If enabled, defines the high alarm limit.
The high alarm may be selected as
shutdown or loaddump with “alarm
level” parameter.
High Warning Level
x
0
10000
If defined, defines the high warning.
16.7. SENDER CONFIGURATION