D-500L Firmware V-5.8
K35D03-EN - 100 -
The parameters below define the functions of relay outputs. The unit has 8 relay outputs. All relays have
programmable functions, selected from a list.
Relays may be extended up to 40 using
Relay Extension Modules
.. Other relays are in the optional
Extension Modules.
Parameter Definition
Factory
set
Terminal
number
Description
Relay-01
3
4
Factory set as Crank Relay output
Relay-02
1
5
Factory set as Fuel Relay output
Relay-03
2
6
Factory set as Horn Relay output
Relay-04
8
7
Factory set as Preheat Relay output
Relay-05
4
8
Factory set as Stop Relay output
Relay-06
7
9
Factory set as Idle Speed Relay output
Relay-07
6
72
Factory set as Mains Contactor Relay output
Relay-08
5
51
Factory set as Genset Contactor Relay output
Relay-09
1
-
Relay extension module
– 1
Relay-10
1
-
Relay extension module
– 1
Relay-11
1
-
Relay extension module
– 1
Relay-12
1
-
Relay extension module
– 1
Relay-13
1
-
Relay extension module
– 1
Relay-14
1
-
Relay extension module
– 1
Relay-15
1
-
Relay extension module
– 1
Relay-16
1
-
Relay extension module
– 1
Relay-17
1
-
Relay extension module
– 2
Relay-18
1
-
Relay extension module
– 2
Relay-19
1
-
Relay extension module
– 2
Relay-20
1
-
Relay extension module - 2
Relay-21
1
-
Relay extension module - 2
Relay-22
1
-
Relay extension module - 2
Relay-23
1
-
Relay extension module - 2
Relay-24
1
-
Relay extension module - 2
Relay-25
1
-
Relay extension module - 3
Relay-26
1
-
Relay extension module - 3
Relay-27
1
-
Relay extension module - 3
Relay-28
1
-
Relay extension module - 3
Relay-29
1
-
Relay extension module - 3
Relay-30
1
-
Relay extension module - 3
Relay-31
1
-
Relay extension module - 3
Relay-32
1
-
Relay extension module - 3
Relay-33
1
-
Relay extension module - 4
Relay-34
1
-
Relay extension module - 4
Relay-35
1
-
Relay extension module - 4
Relay-36
1
-
Relay extension module - 4
Relay-37
1
-
Relay extension module - 4
Relay-38
1
-
Relay extension module - 4
Relay-39
1
-
Relay extension module - 4
Relay-40
1
-
Relay extension module - 4
Below is a short list for reference purposes. Please use
the RainbowPlus program for complete selection list.
16.9. OUTPUT CONFIGURATION