D-500L Firmware V-5.8
K35D03-EN - 107 -
Below is a table showing the tripping delay in function of the percent load level (with TMS=36):
100% unlimited
170% 73s
240% 18s
110% 3600s
180% 56s
250% 16s
120% 900s
190% 44s
260% 14s
130% 400s
200% 36s
270% 12s
140% 225s
210% 30s
280% 11s
150% 144s
220% 25s
290% 10s
160% 100s
230% 21s
300% 9s
Below is the tripping delay curve in function of the load level (with TMS=36):