D-500L Firmware V-5.8
K35D03-EN - 91 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Service-2 Engine Hours
hours
0
5000
250
The
SERVICE REQUEST
led indicator
will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no
SERVICE REQUEST
will
be generated depending on service-2
engine hours.
Service-2 Period
month
0
24
6
The
SERVICE REQUEST
led indicator
will turn on after this amount of time
from the last service. If the period is set
to ‘0’ no
SERVICE REQUEST
will be
indicated depending on Service-2
Period.
Service-2 Alarm Level
-
0
3
0
0:
no action
1:
shutdown alarm
2:
loaddump alarm
3:
warning
Service-3 Engine Hours
hours
0
5000
250
The
SERVICE REQUEST
led indicator
will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no
SERVICE REQUEST
will
be generated depending on service-3
engine hours.
Service-3 Period
month
0
24
6
The
SERVICE REQUEST
led indicator
will turn on after this amount of time
from the last service. If the period is set
to ‘0’ no
SERVICE REQUEST
will be
indicated depending on Service-3
Period.
Service-3 Alarm Level
-
0
3
0
0:
no action
1:
shutdown alarm
2:
loaddump alarm
3:
warning
J1939 Enable
-
0
1
0
0:
The J1939 port is inoperative.
1:
The analog measurements (oil,
temp, and rpm) are picked up from the
ECU. If the ECU communication is lost,
then the engine will be stopped.
J1939 Engine Brand
-
0
15
0
0:
GENERIC
1:
CUMMINS
2:
DETROIT DIESEL
3:
DEUTZ
4:
JOHN DEERE
5:
PERKINS
6:
VOLVO
7:
CATERPILLAR
8:
SCANIA
9:
IVECO
10:
MTU-MDEC
11:
BOSCH
Other values: Reserved. Do not use.
16.3. ENGINE PARAMETERS GROUP (continued)