Table 2-5. Error Code Diagnostic Chart
Error Code
Possible Cause
Check
Solution
00
Analog
density
transducer
out of range
NOTE: Error
Code is
active if
DENTYP is
"1".
1. Densitometer not
used.
2. Incorrect zero or
full scale entered for
densitometer.
3. Densitometer output
is greater than 102%.
4. Density out of
range, densitometer
malfunctioning or mis-
calibrated, wiring
error.
1. Check VAR value
of read code 0
(DEN-LBF3).
1. Check values of
read codes 12 (DFS)
and 13 (DZ).
1. If read code 0 value
is greater than read
code 12;
1. If read code 0 value
is less than read code
13;
1. Place read code 0
in FXD mode. Enter
average density
(paragraph 3.6.2).
1. Enter correct full
scale and zero values
per paragraph 3.6.5.
1. Check wiring.
2. Verify density
3. Check
densitometer.
1. Check wiring.
2. Verify density.
3. Check
densitometer.
SECTION 2
51