1.3.3 Mechanical Dimensions
A
a
b
B
C
0
D
130BB614.10
e
f
a
d
e
130BC205.10
e
f
a
e
130BC246.10
Table 1.5
Power
Height [mm/inch]
Width [mm/inch]
Depth [mm/
inch]
Hole [mm]
Frame
IP class
3x380-480 V
A
A incl.
decoupling
plate
A
B
b
C
D
H1
IP20
0.37-1.5 kW/
0.5-2 hp
195/7.7
273/10.7
183/7.2
75/3
56/2.2
168/6.6
4.5
H2
IP20
2.2-4 kW/
3-5.4 hp
227/8.4
303/11.9
212/8.3
90/3.5
65/2.6
190/7.5
5.5
H3
IP20
5.5-7.5 kW/
7.5-10 hp
255/10
329/13
240/9.4
100/3.9
74/2.9
206/8.1
5.5
H4
IP20
11-15 kW/
15-20 hp
296/11.7
359/14.1
275/10.8
135/5.3
105/4.1
241/9.5
7
H5
IP20
18.5-22 kW/
25-30 hp
334/13.1
402/15.8
314/12.4
150/5.9
120/4.7
255/10
7
H6
IP20
30-45 kW/
40-60 hp
518/20.4
595/23.4
635/25
495/19.5
239/31.5
200/7.9
242/9.5
8.5
H7
IP20
55-75 kW/
100-120 hp
550/21.7
630/24.8
690/27.2
521/20.5
313/12.3
270/10.6
335/13.2
8.5
H8
IP20
90 kW/
120 hp
660/26
800/31.5
631/24.8
375/14.8
330/13
335/13.2
8.5
Table 1.6 Mechanical Dimensions
The dimensions are only for the physical units, but when
installing in an application it is necessary to add space for
free air passage both above and below the units. The
amount of space for free air passage is listed in
Table 1.7
:
Enclosure
Clearance needed for free air passage [mm]
Frame IP class
Above unit
Below unit
H1
20
100
100
H2
20
100
100
H3
20
100
100
H4
20
100
100
H5
20
100
100
H6
20
200
200
H7
20
200
200
H8
20
225
225
Table 1.7 Clearance Needed for Free Air Passage
Quick Guide
VLT
®
HVAC Basic Drive Cascade Controller Quick Guide
MG18F402 - VLT
®