D. Operation keys and indicator lights (LEDs)
Key
Function
13
Hand On
Starts the frequency converter in local control.
•
An external stop signal by control input or
serial communication overrides the local
hand on.
14
Off/Reset
Stops the motor but does not remove power
to the frequency converter or resets the
frequency converter manually after a fault has
been cleared. If in alarm mode, the alarm is
reset if the alarm condition is removed.
15
Auto On
Puts the system in remote operational mode.
•
Responds to an external start command by
control terminals or serial communication.
Table 5.4 Legend to
, Section D
WARNING
ELECTRICAL HAZARD
Even after pressing the [Off/Reset] key, voltage is present
at the terminals of the frequency converter. Pressing the
[Off/Reset] key does not disconnect the frequency
converter from mains. Touching live parts can result in
death or serious injury.
•
Do not touch any live parts.
5.3.2 The Right-key Function on NLCP
Press [
►
] to edit any of the 4 digits on the display
individually. When pressing [
►
] once, the cursor moves to
the first digit, and the digit starts flashing as shown in
. Press the [
▲
] [
▼
] to change the value.
Pressing [
►
] does not change the value of the digits, or
move the decimal point.
130BC440.10
Setup 1
Setup 1
Setup 1
Setup 1
Setup 1
Illustration 5.3 Right-key Function
[
►
] can also be used for moving between parameter
groups. When in
Main Menu
, press [
►
] to move to the first
parameter in the next parameter group (for example, move
from
parameter 0-03 Regional Settings
[0] International
to
parameter 1-00 Configuration Mode
[0] Open loop
).
NOTICE
During start-up, the LCP shows the message
INITIALISING
.
When this message is no longer shown, the frequency
converter is ready for operation. Adding or removing
options can extend the duration of start-up.
5.3.3 Quick Menu on NLCP
The
Quick Menu
gives easy access to the most frequently
used parameters.
1.
To enter
Quick Menu
, press [Menu] until the
indicator in the display is placed above
Quick
Menu
.
2.
Press [
▲
] [
▼
] to select either QM1 or QM2, then
press [OK].
3.
Press [
▲
] [
▼
] to browse through the parameters in
Quick Menu
.
4.
Press [OK] to select a parameter.
5.
Press [
▲
] [
▼
] to change the value of a parameter
setting.
6.
Press [OK] to accept the change.