No.
Description
Warning
Alarm
Trip lock
Cause
Err.
A wrong password was entered
–
–
–
Occurs when using a wrong password for changing a
password-protected parameter.
Table 8.1 Warnings and Alarms Code List
1) Mains distortions may cause these faults. Installing a Danfoss line filter may rectify this problem.
2) This alarm cannot be reset via parameter 14-20 Reset Mode automatically.
For diagnosis, read out the alarm words, warning words, and extended status words.
Bit
Hex
Dec
Alarm word
(
parameter 1
6-90 Alarm
Word
)
Alarm word
2
(
parameter
16-91 Alarm
Word 2
)
Alarm word
3
(
parameter 1
6-97 Alarm
Word 3
)
Warning word
(
parameter 16-
92 Warning
Word
)
Warning word
2
(
parameter 16
-93 Warning
Word 2
)
Extended
status word
(
parameter 16-
94 Ext. Status
Word
)
Extended
status word 2
(
parameter 16-95 Ext
. Status Word 2
)
0
000000
01
1
Brake check
Reserved
STO function
fault
Reserved
Reserved
Ramping
Off
1
000000
02
2
Pwr. card
temp
Gate drive
voltage fault
MM alarm
Pwr. card
temp
Reserved
AMA tuning
Hand/Auto
2
000000
04
4
Earth fault
Reserved
Reserved
Reserved
Reserved
Start CW/CCW Profibus OFF1 active
3
000000
08
8
Ctrl. card
temp
Reserved
Reserved
Ctrl. card temp
Reserved
Slowdown
Profibus OFF2 active
4
000000
10
16
Ctrl. word
TO
Reserved
Reserved
Ctrl. word TO
Reserved
Catchup
Profibus OFF3 active
5
000000
20
32
Overcurrent
Reserved
Reserved
Overcurrent
Reserved
Feedback high
Reserved
6
000000
40
64
Torque limit
Reserved
Reserved
Torque limit
Reserved
Feedback low
Reserved
7
000000
80
128
Motor Th.
over
Reserved
Reserved
Motor Th. over
Reserved
Output current
high
Control ready
8
000001
00
256
Motor ETR
over
Broken belt
Reserved
Motor ETR
over
Broken belt
Output current
low
Frequency converter
ready
9
000002
00
512
Inverter
overld.
Reserved
Reserved
Inverter overld.
Reserved
Output freq.
high
Quick stop
10
000004
00
1024
DC
undervolt.
Start failed
Reserved
DC undervolt.
Reserved
Output freq.
low
DC brake
11
000008
00
2048
DC overvolt. Speed limit
Reserved
DC overvolt.
Reserved
Brake check OK
Stop
12
000010
00
4096
Short circuit
External
interlock
Reserved
Reserved
Reserved
Braking max
Reserved
13
000020
00
8192
Reserved
Reserved
Reserved
Reserved
Reserved
Braking
Freeze output
request
14
000040
00
16384
Mains ph.
loss
Reserved
Reserved
Mains ph. loss
Reserved
Reserved
Freeze output
15
000080
00
32768
AMA not OK
Reserved
Reserved
No motor
Auto DC
braking
OVC active
Jog request
16
000100
00
65536
Live zero
error
Reserved
Reserved
Live zero error
Reserved
AC brake
Jog
17
000200
00
131072
Internal fault
Reserved
Reserved
Reserved
Reserved
Reserved
Start request
Maintenance, Diagnostics, a...
Operating Guide
MG07A402