selections, fault log, alarm log, and other
monitoring functions.
•
Manual initialization erases all motor,
programming, localization, and monitoring data
and restores factory default settings.
Recommended initialization procedure, via
parameter 14-22 Operation Mode
1.
Select
parameter 14-22 Operation Mode
and press
[OK].
2.
Select
[2] Initialisation
and press [OK].
3.
Remove power to the unit and wait until the
display turns off.
4.
Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
5.
Alarm 80, Drive initialised to default value
is shown.
6.
Press [Reset] to return to operation mode.
Manual initialization procedure
1.
Remove power to the unit and wait until the
display turns off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time on the GLCP, or press [Menu] and
[OK] at the same time on the NLCP while
applying power to the unit (approximately 5 s or
until a click is heard and the fan starts).
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialization does not reset the following
frequency converter information:
•
Parameter 15-00 Operating hours
•
Parameter 15-03 Power Up's
•
Parameter 15-04 Over Temp's
•
Parameter 15-05 Over Volt's
5.4 Basic Programming
5.4.1 Asynchronous Motor Set-up
Enter the following motor data in the listed order. Find the
information on the motor nameplate.
1.
Parameter 1-20 Motor Power
.
2.
Parameter 1-22 Motor Voltage
.
3.
Parameter 1-23 Motor Frequency
.
4.
Parameter 1-24 Motor Current
.
5.
Parameter 1-25 Motor Nominal Speed
.
For optimum performance in VVC
+
mode, extra motor data
is required to set up the following parameters.
6.
Parameter 1-30 Stator Resistance (Rs)
.
7.
Parameter 1-31 Rotor Resistance (Rr)
.
8.
Parameter 1-33 Stator Leakage Reactance (X1)
.
9.
Parameter 1-35 Main Reactance (Xh)
.
The data is found in the motor datasheet (this data is
typically not available on the motor nameplate). Run a
complete AMA using
parameter 1-29 Automatic Motor
Adaption (AMA)
[1] Enable Complete AMA
or enter the
parameters manually.
Application-specific adjustment when running VVC
+
VVC
+
is the most robust control mode. In most situations,
it provides optimum performance without further
adjustments. Run a complete AMA for best performance.
5.4.2 PM Motor Set-up in VVC
+
Initial programming steps
1.
Set
parameter 1-10 Motor Construction
to the
following options to activate PM motor operation:
1a
[1] PM, non salient SPM
1b
[3] PM, salient IPM
2.
Select
[0] Open Loop
in
parameter 1-00 Configu-
ration Mode
.
NOTICE
Encoder feedback is not supported for PM motors.
Programming motor data
After selecting 1 of the PM motor options in
parameter 1-10 Motor Construction
, the PM motor-related
parameters in
parameter groups 1-2* Motor Data
,
1-3* Adv.
Motor Data
, and
1-4* Adv. Motor Data II
are active.
Find the information on the motor nameplate and in the
motor datasheet.
Program the following parameters in the listed order:
1.
Parameter 1-24 Motor Current
.
2.
Parameter 1-26 Motor Cont. Rated Torque
.
3.
Parameter 1-25 Motor Nominal Speed
.
4.
Parameter 1-39 Motor Poles
.
5.
Parameter 1-30 Stator Resistance (Rs)
.
Enter line-to-common stator winding resistance
(Rs). If only line-line data is available, divide the
line-line value by 2 to achieve the line-to-
common (starpoint) value.
It is also possible to measure the value with an
ohmmeter, which also takes the resistance of the
cable into account. Divide the measured value by
2 and enter the result.
6.
Parameter 1-37 d-axis Inductance (Ld)
.
Commissioning
Operating Guide
MG07A402