130BE425.12
24 V source
37
38
+
-
12
55
1
1
Safety device
Illustration 6.5 STO Wiring, External Supply
3.
Complete the wiring according to the instructions
in
chapter 4 Electrical Installation
, and:
3a
Eliminate short circuit risks.
3b
Ensure that the STO cables are shielded
if they are longer than 20 m (65.6 ft) or
outside the cabinet.
3c
Connect the safety device directly to
terminals 37 and 38.
6.3 STO Commissioning
6.3.1 Activation of Safe Torque Off
To activate the STO function, remove the voltage at
terminals 37 and 38 of the frequency converter.
When STO is activated, the frequency converter issues
alarm 68, Safe Torque Off
or
warning 68, Safe Torque Off
,
trips the unit, and coasts the motor to stop. Use the STO
function to stop the frequency converter in emergency
stop situations. In normal operating mode when STO is not
required, use the standard stop function instead.
NOTICE
If STO is activated while the frequency converter issues
warning 8, DC undervoltage
or
alarm 8, DC undervoltage
,
the frequency converter skips
alarm 68, Safe Torque Off
,
but the STO operation is not affected.
6.3.2 Deactivation of Safe Torque Off
Follow the instructions in
to deactivate the STO
function and resume normal operation based on the
restart mode of the STO function.
WARNING
RISK OF INJURY OR DEATH
Reapplying 24 V DC supply to either terminal 37 or 38
terminates the SIL2 STO state, potentially starting the
motor. Unexpected motor start may cause personal
injuries or death.
•
Ensure that all safety measures are taken before
reapplying 24 V DC supply to terminals 37 and
38.
Restart
mode
Steps to deactivate STO
and resume normal
operation
Restart mode configu-
ration
Manual
restart
1. Reapply 24 V DC
supply to terminals 37
and 38.
2. Initiate a reset signal
(via fieldbus, digital
I/O, or [Reset]/[Off
Reset] key on the
LCP).
Default setting.
Parameter 5-19 Terminal
37/38 Safe Torque Off
=
[1]
Safe Torque Off Alarm
Automatic
restart
Reapply 24 V DC supply
to terminals 37 and 38.
Parameter 5-19 Terminal
37/38 Safe Torque Off
=
[3]
Safe Torque Off Warning
.
Table 6.2 STO Deactivation
6.3.3 STO Commissioning Test
After installation and before first operation, perform a
commissioning test of the installation using STO.
Perform the test again after each modification of the
installation or application involving the STO.
NOTICE
A successful commissioning test of the STO function is
required after the initial installation, and after each
subsequent change to the installation.
To perform a commissioning test:
•
Follow the instructions in
STO Applications in Manual Restart Mode
if STO is
set to manual restart mode.
•
Follow the instructions in
STO Applications in Automatic Restart Mode
if STO
is set to automatic restart mode.
Safe Torque Off (STO)
Operating Guide
MG07A402