4.8 Control Wiring
4.8.1 Control Terminal Types
shows the removable frequency converter
connectors. Terminal functions and default settings are
summarized in
and
130BE212.10
1
2
3
Illustration 4.8 Control Terminal Locations
130BE214.10
37 38 12 13 18 19 27 29 32 33
61
42 53 54 50 55
68 69
1
3
2
Illustration 4.9 Terminal Numbers
See
chapter 9.6 Control Input/Output and Control Data
for
terminal ratings details.
Terminal
Parameter
Default
setting
Description
Digital I/O, Pulse I/O, Encoder
12, 13
–
+24 V DC
24 V DC supply
voltage.
Maximum
output current is
100 mA for all
24 V loads.
18
Parameter 5-10 Ter
minal 18 Digital
Input
[8] Start
Digital inputs.
19
Parameter 5-11 Ter
minal 19 Digital
Input
[10]
Reversing
Terminal
Parameter
Default
setting
Description
27
Parameter 5-12 Ter
minal 27 Digital
Input
parameter 5-30 Ter
minal 27 Digital
Output
DI [2] Coast
inverse
DO [0] No
operation
Selectable for
either digital
input, digital
output, or pulse
output. The
default setting is
digital input.
29
Parameter 5-13 Ter
minal 29 Digital
Input
[14] Jog
Digital input.
32
Parameter 5-14 Ter
minal 32 Digital
Input
[0] No
operation
Digital input, 24
V encoder.
Terminal 33 can
be used for
pulse input.
33
Parameter 5-15 Ter
minal 33 Digital
Input
[16] Preset ref
bit 0
37, 38
–
STO
Functional safety
inputs.
Analog inputs/outputs
42
Parameter 6-91 Ter
minal 42 Analog
Output
[0] No
operation
Programmable
analog output.
The analog
signal is 0–20
mA or 4–20 mA
at a maximum
of 500
Ω
. Can
also be
configured as
digital outputs.
50
–
+10 V DC
10 V DC analog
supply voltage.
15 mA
maximum
commonly used
for potenti-
ometer or
thermistor.
53
6-1* parameter
group
–
Analog input.
Only voltage
mode is
supported. It can
also be used as
digital input.
54
6-2* parameter
group
–
Analog input.
Selectable
between voltage
or current mode.
55
–
–
Common for
analog input.
Table 4.1 Terminal Descriptions - Digital Inputs/Outpus,
Analog Input/Outputs
Electrical Installation
VLT
®
Midi Drive FC 280
16
Danfoss A/S © 11/2015 All rights reserved.
MG07A102