[28] Catch up
Select Catch up/Slow down to increase or
reduce the resulting reference value by the
percentage set in
3-12 Catch Up/Slow Down
Value
[29] Slow down
Same as Catch up [28]
[32] Pulse input
(only terminal
33)
Select Pulse input when using a pulse
sequence as either reference or feedback.
Scaling is done in parameter group
5-5*
Pulse Input
[34] Ramp bit 0
Logic 0=Ramp1, see parameter group
3-4*
Ramp1
Logic 1=Ramp2, see parameter group
3-5*
Ramp2
.
[60] Counter A
(up)
Input for counter A.
[61] Counter A
(down)
Input for counter A.
[62] Reset counter
A
Input for reset of counter A.
[63] Counter B
(up)
Input for counter B.
[64] Counter B
(down)
Input for counter B.
[65] Reset counter
B
Input for reset of counter B.
5-10 Terminal 18 Digital Input
Option:
Function:
[8]
*
Start Select function from available digital input range.
See parameter group
5-1* Digital Inputs
for choices.
5-11 Terminal 19 Digital Input
Option:
Function:
[10]
*
Reversing Select function from available digital input
range.
See parameter group
5-1* Digital Inputs
for
choices.
5-12 Terminal 27 Digital Input
Option:
Function:
[1]
*
Reset Select function from available digital input range.
See parameter group
5-1* Digital Inputs
* for choices.
5-13 Terminal 29 Digital Input
Option:
Function:
[14]
*
Jog Select function from available digital input range.
See parameter group
5-1* Digital Inputs
for choices.
5-15 Terminal 33 Digital Input
Option:
Function:
[16]
*
Preset bit 0 Select function from available digital input
range.
See parameter group
5-1* Digital Inputs
for
choices.
4.6.3 5-3* Digital Outputs
5-34 On delay, Terminal 42 Digital Output
Range:
Function:
0.01 s
*
[0.00-600.00 s]
5-35 Off delay, Terminal 42 Digital Output
Range:
Function:
0.01 s
*
[0.00-600.00 s]
4.6.4 5-4* Relays
Parameter group for configuring timing and output
functions for relays.
[0]
No Operation
Default for all digital and relay outputs.
[1]
Control Ready
Control board receives supply voltage.
[2]
Drive Ready
Frequency converter is ready for
operation and applies supply signal on
control board.
[3]
Drive Ready,
Remote
Frequency converter is ready for
operation in Auto On-mode.
[4]
Enable/No
Warning
Frequency converter is ready for
operation. No start or stop command is
given. No warnings are present.
[5]
Drive Running
Motor is running.
[6]
Running/No
Warning
Motor runs, and no warning are
present.
[7]
Run in Range/No
Warning
Motor runs within programmed current
ranges, see
4-50 Warning Current Low
and
4-51 Warning Current High
. No
warnings are present.
[8]
Run on ref/No
Warning
Motor runs at reference speed.
[9]
Alarm
An alarm activates output.
[10] Alarm on Warning An alarm or warning activates output.
[12] Out of Current
Range
Motor current is outside range set in
4-50 Warning Current Low
and
4-51
Warning Current High
.
[13] Below Current,
low
Motor current is lower than set in
4-50
Warning Current Low
.
[14] Above Current,
high
Motor current is higher than set in
4-51
Warning Current High
.
[16] Below Frequency,
low
Motor speed is lower than set in
4-40
Warning Frequency Low
.
[17] Above Frequency,
high
Motor speed is higher than set in
4-41
Warning Frequency High
.
[19] Below Feedback,
low
Feedback is lower than set in
4-56
Warning Feedback Low
.
[20] Above Feedback,
high
Feedback is higher than set in
4-57
Warning Feedback High
.
[21] Thermal Warning
Thermal warning is present when
temperature exceeds limit in motor,
frequency converter, brake resistor or
thermistor.
Parameter Descriptions
VLT
®
Micro Drive FC 51 Programming Guide
MG02C602 - VLT
®
is a registered Danfoss trademark
29
4