6-0* Analog I/O Mode
6-00 Live Zero Timeout Time
1-99 s *10 s
6-01 Live Zero TimeoutFunction
*[0] Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max speed
[5] Stop and trip
6-1* Analog Input 1
6-10 Terminal 53 Low Voltage
0.00-9.99 V *0.07 V
6-11 Terminal 53 High Voltage
0.01-10.00 V *10.00 V
6-12 Terminal 53 Low Current
0.00-19.99 mA *0.14 mA
6-13 Terminal 53 High Current
0.01-20.00 mA *20.00 mA
6-14 Term. 53 Low Ref./Feedb.
Value
-4999-4999 *0.000
6-15 Term. 53 High Ref./Feedb.
Value
-4999-4999 *50.000
6-16 Terminal 53 Filter Time
Constant
0.01-10.00 s *0.01 s
6-19 Terminal 53 mode
*[0] Voltage mode
[1] Current mode
6-2* Analog Input 2
6-22 Terminal 60 Low Current
0.00-19.99 mA *0.14 mA
6-23 Terminal 60 High Current
0.01-20.00 mA *20.00 mA
6-24 Term. 60 Low Ref./Feedb.
Value
-4999-4999 *0.000
6-25 Term. 60 High Ref./Feedb.
Value
-4999-4999 *50.00
6-26 Terminal 60 Filter Time
Constant
0.01-10.00 s *0.01 s
6-8* LCP potentiometer
6-80 LCP LCP Potmeter Enable
[0] Disabled
[1] * Enable
6-81 LCP potm. Low Reference
-4999-4999 *0.000
6-82 LCP potm. High Reference
-4999-4999 *50.00
6-9* Analog Output xx
6-90 Terminal 42 Mode
*[0] 0-20 mA
[1] 4-20 mA
[2] Digital Output
6-91 Terminal 42 Analog Output
*[0] No operation
[10] Output Frequency
[11] Reference
[12] Feedback
[13] Motor Current
[16] Power
[20] Bus Reference
6-92 Terminal 42 Digital Output
See par. 5-40
*[0] No Operation
[80] SL Digital Output A
6-93 Terminal 42 Output Min
Scale
0.00-200.0%
*0.00%
6-94 Terminal 42 Output Max
Scale
0.00-200.0% *100.0%
7-** Controllers
7-2* Process Ctrl. Feedb
7-20 Process CL Feedback 1
Resource
*[0] NoFunction
[1] Analog Input 53
[2] Analog input 60
[8] PulseInput33
[11] LocalBusRef
7-3* Process PI
Ctrl. 7-30 Process PI Normal/
Inverse Ctrl
*[0] Normal
[1] Inverse
7-31 Process PI Anti Windup
[0] Disable
*[1] Enable
7-32 Process PI Start Speed
0.0-200.0 Hz *0.0 Hz
7-33 Process PI Proportional Gain
0.00-10.00 *0.01
7-34 Process PI Integral Time
0.10-9999 s *9999 s
7-38 Process PI Feed Forward
Factor
0-400% *0%
7-39 On Reference Bandwidth
0-200% *5%
8-** Comm. and Options
8-0* General Settings
8-01 Control Site
*[0] Digital and ControlWord
[1] Digital only
[2] ControlWord only
8-02 Control Word Source
[0] None
*[1] FC RS485
8-03 Control Word Timeout Time
0.1-6500 s *1.0 s
8-04 Control Word Timeout
Function
*[0] Off
[1] Freeze Output
[2] Stop
[3] Jogging
[4] Max. Speed
[5] Stop and trip
8-06 Reset Control Word Timeout
*[0] No Function
[1] Do reset
8-3* FC Port Settings
8-30 Protocol
*[0] FC
[2] Modbus
8-31 Address
1-247 *1
8-32 FC Port Baud Rate
[0] 2400 Baud
[1] 4800 Baud
*[2] 9600 Baud For choosing FC
bus in 8-30
* [3] 19200 Baud For choosing
FC bus in 8-30
*[4] 38400 Baud
8-33 FC Port Parity
*[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
0.001-0.5 *0.010 s
8-36 Max Response Delay
0.100-10.00 s *5.000 s
8-4* FC MC protocol set
8-43 FC Port PCD Read Configu-
ration
*[0] None Expressionlimit
[1] [1500] Operation Hours
[2] [1501] Running Hours
[3] [1502] kWh Counter
[4] [1600] Control Word
[5] [1601] Reference [Unit]
[6] [1602] Reference %
[7] [1603] Status Word
[8] [1605] Main Actual Value [%]
[9] [1609] Custom Readout
[10] [1610] Power [kW]
[11] [1611] Power [hp]
[12] [1612] Motor Voltage
[13] [1613] Frequency
[14] [1614] Motor Current
[15] [1615] Frequency [%]
[16] [1618] Motor Thermal
[17] [1630] DC Link Voltage
[18] [1634] Heatsink Temp.
[19] [1635] Inverter Thermal
[20] [1638] SL Controller State
[21] [1650] External Reference
[22] [1651] Pulse Reference
[23] [1652] Feedback [Unit]
[24] [1660] Digital Input
18,19,27,33
[25] [1661] Digtial Input 29
[26] [1662] Analog Input 53(V)
[27] [1663] Analog Input 53(mA)
[28] [1664] Analog Input 60
[29] [1665] Analog Output 42
[mA]
[30] [1668] Freq. Input 33 [Hz]
[31] [1671] Relay Output [bin]
[32] [1672] Counter A
[33] [1673] Counter[34] [1690]
Alarm Word
[34] [1690] Alarm Word
[35] [1692] Warning Word
[36] [1694] Ext. Status Word
8-5* Digital/Bus
8-50 Coasting Select
[0] DigitalInput
[1] Bus
[2] LogicAnd
*[3] LogicOr
8-51 Quick Stop Select
See par. 8-50 * [3] LogicOr
8-52 DC Brake Select
See par. 8-50 * [3] LogicOr
8-53 Start Select
See par. 8-50 * [3] LogicOr
8-54 Reversing Select
See par. 8-50 * [3] LogicOr
8-55 Set-up Select
See par. 8-50 * [3] LogicOr
8-56 Preset Reference Select
See par. 8-50 * [3] LogicOr
8-8X Bus communication
Diagnostics
8-80 Bus Message Count
0-0 N/A *0 N/A
8-81 Bus Error Count
0-0 N/A *0 N/A
8-82 Slave Messages Rcvd
0-0 N/A *0 N/A
8-83 Slave Error Count
0-0 N/A *0 N/A
Table 5.3
Parameter Lists
VLT
®
Micro Drive FC 51 Programming Guide
52
MG02C602 - VLT
®
is a registered Danfoss trademark
5
5