4.1.3 0-5* Copy/Save
0-50 LCP Copy
Option:
Function:
The detachable LCP of the frequency
converter can be used for storing setups,
and thus for transferring data when
moving parameter settings from one
frequency converter to another.
NOTE
LCP Copy
can only be activated from
the LCP and ONLY when the motor
is coasted.
[1] All to LCP
Copy all setups from the frequency
converter into the LCP.
[2] All from LCP
Copy all setups from LCP to frequency
converter.
[3] Size independent
from LCP
Copy non motor size dependent data
from LCP to frequency converter.
0-51 Set-up Copy
Option:
Function:
Use this function to copy a set-up content
into the
Edit Set-up
.
In order to be able to make a set-up copy
ensure that
•
the motor is coasted
•
0-10 Active Set-up
,
Active Set-up
, is
set to either
[1] Set-up 1
or
[2] Set-
up 2
NOTE
The keyboard/parameter database are
blocked while Set-up Copy is running.
[0 ]
*
No Copy
Copy function is inactive
[1]
Copy from
Set-up 1
Copy from
Set-up 1
to edit set-up chosen in
0-11 Edit Set-up
.
[2]
Copy from
Set-up 2
Copy from
Set-up 2
to edit set-up chosen in
0-11 Edit Set-up
.
[9]
Copy from
Factory Set-
up
Copy from Factory Settings to edit set-up
chosen in
0-11 Edit set-up
.
4.1.4 0-6* Password
0-60 (Main) Menu Password
Range:
Function:
Use password for protection against unintended
change of sensitive parameters, eg. motor
parameters.
0
*
[0-999] Enter the password for access to Main Menu via
the [Main Menu] key. Select the number that
should allow for changing other parameter values.
0
means there is no password.
NOTE
A password has affect on the LCP - not on the bus
communication.
NOTE
Pressing [Menu], [OK] and [
▼
] will unlock the password.
This will automatically enter the parameter editing screen
in Quick Menu or Main Menu.
0-61 Access to Main/Quick Menu w/o Password
Option:
Function:
[0]
*
Full access
Select
[0] Full Access
to disable the
password in
0-60 (Main) Menu Password
.
[1]
LCP: Read Only Select
[1] Read Only
to block unauthorized
editing of Main/Quick menu parameter.
[2]
LCP: No Access Select
[2] No Access
to block unauthorized
editing and viewing of Main/Quick menu
parameter.
Parameter Descriptions
VLT
®
Micro Drive FC 51 Programming Guide
MG02C602 - VLT
®
is a registered Danfoss trademark
13
4