9 Specifications
Supply
Rated supply voltage 208-230/240 V (L1, L2) (min 180 V, max 264 V)
Mains frequency 50/60 Hz, single phase
Rated load amperage (RLA) (208 V):
22A, 13 kW/3 t unit
28A, 16 kW/4 t unit
33A, 20 kW/5 t unit
Power Factor @230 V, full load
> 0.98 (98%)
THiD
< 22%
THvD
< 3% (at typical mains impedance)
Earth leakage current (drive and compressor)
<10 mA
Stand-by power consumption
5W
Input power (at 208 V)
13 kW/3 ton unit
4.5 kW
16 kW/4 ton unit
5.6 kW
20 kW/5 ton unit
6.7 kW
Cable length
The maximum allowable cable length between drive and compressor is 7 ft/2 m
Analog inputs (sensor inputs)
Temperature
Pt 1000 sensor (AKS11)
Pressure
Ratio metric input 0.5-4.5 V, input resistance 10 k
Ω
(AKS32)
Digital output (condenser fan motor control), EXT_FAN:
PWM signal speed reference, duty cycle 15-100% speed.
Reversing valve relay, RLY_1:
NC/NO 3-pole relay, max. terminal load 250 V AC/24 V DC, 4 A
EEV Controller output (outdoor unit), EEV_2:
Internal power supply 24 V DC with ground RS-485 serial interface (Modbus)
RS-485 serial communication interface, MASTER and EEV_1:
According to Electronics Industry Association (EIA) standard.
Minimum power cycling time
The variable speed drive is equipped with an inrush circuit, limiting the starting (inrush) current when the system is
powered up.
CAUTION
Frequent cycling of power to the drive can damage the drive! Wait at least 5 minutes between cycles (connecting and
disconnecting power to the drive).
The OEM must place an equivalent notice on the unit!
Internal cooling fan
High performance variable speed cooling fan, supply voltage 16 V. Nominal operating point 74 CFM (126 m3/h) @ 89Pa
static pressure.
Specifications
VLT
®
Inverter Scroll CDS 801 Operating Instructions
48
MG10V402 - VLT
®
is a registered Danfoss trademark