6.4 Thermo Controller Register Overview (Node 162)
All registers with name type of THERMO_SETUP_XXXXXX are stored in eeprom and can only be overwritten 1 million times.
The same applies for 40201 - THERMO_IN_COMPRESSOR_MODE and 40202 - THERMO_IN_FAN_MODE, see
.
Address
Name
Description
40201
THERMO_IN_MODE
System control mode:
0 = off
1 = AC
2 = HP
3 = Defrost
40202
THERMO_IN_COMPRESSOR_MODE
Compressor capacity control:
0 = Single loop ; Room temp. control
2 = External speed control
40203
THERMO_IN_FAN_MODE
Condenser/outdoor fan control:
0 = Optimal compressor COP
1 = Delta T
2 = External speed control
3 = Bypass
40204
THERMO_IN_PC
Condensing pressure [bar] from sensor connected to drive
(absolute)
40206
THERMO_IN_P0
Suction pressure [bar] from sensor connected to drive
(absolute)
40208
THERMO_IN_ROOM_TEMPERATURE
Room temperature [
°
C] from OEM controller
40210
THERMO_IN_ROOM_TEMPERATURE_SET_POINT
Room temperature [
°
C] setpoint from OEM controller
40212
THERMO_IN_COMPRESSOR_EXTERNAL_SPEED_PCT
Compressor external speed % command from OEM controller
0% = off
1% = Min speed. 100% = Max speed
40213
THERMO_IN_FAN_EXTERNAL_SPEED_PCT
Condenser outdoor fan external speed % command from OEM
controller
40214
THERMO_IN_DISCHARGE_TEMPERATURE
Compressor discharge temperature [
°
C] from sensor connected
to drive
40216
THERMO_IN_AMBIENT_TEMPERATURE
Ambient temperature [
°
C] from sensor connected to drive
40218
THERMO_IN_S4
Temperature [
°
C] signal from indoor EEV (not active yet)
40220
THERMO_IN_DRIVE_TEMPERATURE
Drive temperature [
°
C]
40222
THERMO_IN_LINE_VOLT
Input voltage to drive
40224
THERMO_IN_OIL_RETURN_SWITCH_ON
0: off, 1: on, will be reset to off when drive has been powered
off
40225
THERMO_IN_EXTERNAL_AMBIENT_TEMPERATURE
[
°C
] Ambient temperature provided via Modbus from OEM
controller.
40301
THERMO_OUT_COMPRESSOR_SPEED_HZ
Compressor speed command to motor control/drive
40303
THERMO_OUT_FAN_SPEED_PCT
Fan speed command to outdoor fan
0% to 100%
40305
THERMO_OUT_FOUR_WAY_VALVE
Four way valve control to set the system in AC or HP mode
40306
THERMO_OUT_START_EEV_INDOOR
Command register to indoor EEV
0 = stop
1 = start
40307
THERMO_OUT_START_EEV_OUTDOOR
Command register to outdoor EEV
0 = stop
1 = start