3.6.4 Sensor Connections
Connect the sensors as marked on the PCB, see
Aux. temperature sensor (S aux.) (if applicable)
Compressor discharge temperature (Sd)
Ambient temperature (S amb.)
Compressor suction pressure (P0)
Compressor discharge pressure (Pc)
175ZB048.11
P_C
P_O
S_D
S_A
UX
S_A
MBIENT
Illustration 3.9 Sensor Connections
3.6.5 4-way Reversing Valve Connection
The relay for the 4-way reversing valve is connected as
shown and marked on the PCB, see
Max. load:
250 V AC, 4 A
24 V DC, 4 A
See
3.6.10 Allocation of Connector Pins
.
175ZB049.11
RL
Y_1
Illustration 3.10 4-way Reversing Valve Connection
3.6.6 Condenser Fan Motor Control
Connection (EXT_FAN)
Two different control signals are available, 0-10 V (max.
current 20 mA) analogue output and 24 V PWM duty cycle
with scalable frequency, see Modbus register description in
. Connect the control signal of the
condenser fan (or any other external device like a
circulator pump) as shown and marked on the PCB, see
175ZB051.11
EX
T_F
AN
Illustration 3.11 Condenser Fan Motor Control Connection (EXT-
Fan)
3.6.7 EEV Controller (HP Mode) Connection
(EEV_2)
Connect the EEV Controller as shown and marked on the
PBC, see
175ZB099.11
EE
V_2
Illustration 3.12 EEV_2 Controller Connection
Electrical Installation
VLT
®
Inverter Scroll CDS 801 Operating Instructions
18
MG10V402 - VLT
®
is a registered Danfoss trademark
3