Address
Name
Description
40308
THERMO_OUT_TRACKING_ERROR_PCT
If the compressor is running in external speed % control mode
the tracking error is calculated
The Tracking error is the difference between actual compressor
speed % and external speed % command
If not running external speed, the tracking error is set to 0
40309
THERMO_OUT_POWER_PCT
Actual Drive power in % of nominal power
40401
THERMO_SETUP_UNITTYPE
Unit type:
0 = 3 Ton
1 = 4 Ton
2 = 5 Ton
40402
THERMO_SETUP_SYSTEM_CONFIGURATION
System Configuration
1 = ID1 (not active)
2 = ID2 AC/HP reversible
3 = ID3 (not active)
4 = ID4 GSHP reversible
5 = ID5 (not active)
6 = ID6 AC only
40403
THERMO_SETUP_COMPRESSOR_MINIMUM_SPEED_HZ
Minimum compressor speed
40404
THERMO_SETUP_COMPRESSOR_MAXIMUM_SPPED_HZ
Maximum compressor speed
40405
THERMO_SETUP_DELTA_HZ_PER_SEC
Allowed speed rate of change in Hz pr. s
40407
THERMO_SETUP_DELTA_TEMP
Delta temperature setting for fan “Delta T” control mode
40409
THERMO_SETUP_OIL_LOSS_TRIG_TIME_SEC
When running below oil return speed for more than this time,
oil return is initiated
40410
THERMO_SETUP_OIL_RETURN_SPEED_HZ
Defined oil return speed
40411
THERMO_SETUP_OIL_RETURN_HOLD_TIME_SEC
Hold time for running at oil return speed
40412
THERMO_SETUP_START_UP_SPEED_HZ
Start up speed for system
40413
THERMO_SETUP_START_UP_HOLD_TIME_SEC
Hold time for start up speed
40414
THERMO_SETUP_RESTART_TIME_SEC
Minimum Time between repeated starts
40415
THERMO_SETUP_CANCEL_CENTER_HZ_1
Centre frequency #1 for speed range cancellation
40416
THERMO_SETUP_CANCEL_BANDWIDTH_HZ_1
Bandwidth #1 for speed range cancellation
40417
THERMO_SETUP_CANCEL_CENTER_HZ_2
Centre frequency #2 for speed range cancellation
40418
THERMO_SETUP_CANCEL_BANDWIDTH_HZ_2
Bandwidth #2for speed range cancellation
40419
THERMO_SETUP_CANCEL_CENTER_HZ_3
Centre frequency #3 for speed range cancellation
40420
THERMO_SETUP_CANCEL_BANDWIDTH_HZ_3
Bandwidth #3 for speed range cancellation
40421
THERMO_SETUP_CANCEL_CENTER_HZ_4
Centre frequency #4 for speed range cancellation
40422
THERMO_SETUP_CANCEL_BANDWIDTH_HZ_4
Bandwidth #4 for speed range cancellation
40423
THERMO_SETUP_CANCEL_CENTER_HZ_5
Centre frequency #5 for speed range cancellation
40424
THERMO_SETUP_CANCEL_BANDWIDTH_HZ_5
Bandwidth #5 for speed range cancellation
40425
THERMO_SETUP_PI_COMPRESSOR_AC_KP
Proportional gain for AC compressor capacity controller
40427
THERMO_SETUP_PI_COMPRESSOR_AC_TN
Integration time for AC compressor capacity controller
40428
THERMO_SETUP_PI_COMPRESSOR_AC_TT
Tracking time constant for AC compressor capacity controller
40429
THERMO_SETUP_PI_COMPRESSOR_HP_KP
Proportional gain for HP compressor capacity controller
40431
THERMO_SETUP_PI_COMPRESSOR_HP_TN
Integration time for HP compressor capacity controller
40432
THERMO_SETUP_PI_COMPRESSOR_HP_TT
Tracking time constant for HP compressor capacity controller
41609
OUTDOOR_FAN_CAPACITY_PCT_MIN
Minimum duty cycle that will be output by the fan controller
41611
OUTDOOR_FAN_CAPACITY_PCT_MAX
Maximum duty cycle that will be output by the fan controller
41613
OUTDOOR_FAN_CONTROL_SIGNAL_FREQUENCY
Set frequency of the condenser fan PWM signal
40479
THERMO_SETUP_CRANK_CASE_HEATING_ON_TEMP
Ambient temperature where crankcase heating is activated
Table 6.2 Thermo Controller Register Overview (Node 162)