Drive
PK75
P1K5
P2K2
P3K0
P4KO
P5K5
P7K5
P11K
P15K
P18K
Intermittent (3x380–440 V) [A]
2.1
4.07
5.4
6.9
9.2
12
15.4
23
30.8
36.3
Continuous (3x441–480 V) [A]
1.8
3.4
4.4
5.5
6.8
10
12.6
19.1
24
30
Intermittent (3x441–480 V) [A]
2.0
3.7
4.8
6.1
8.3
11
13.9
21
26.4
33
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to Danfoss
2
Efficiency measured at nominal current. For energy efficiency class, see
. For part load losses, see Danfoss
website.
Table 17: 3x380–480 V AC, 22–90 kW (30–125 hp), Enclosure Sizes I6–I8
Drive
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Typical shaft output [kW]
22
30
37
45
55
75
90
Typical shaft output [hp]
30
40
50
60
70
100
125
Protection rating IP54
I6
I6
I6
I7
I7
I8
I8
Maximum cable size in terminals
(mains, motor) [mm
2
(AWG)]
35 (2)
35 (2)
35 (2)
50 (1)
50 (1)
95 (3/0)
120 (4/0)
Output current at 40°C (104°F) ambient temperature
Continuous (3x380–440 V) [A]
44
61
73
90
106
147
177
Intermittent (3x380–440 V) [A]
48.4
67.1
80.3
99
116.6
161.7
194.7
Continuous (3x441–480 V) [A]
40
52
65
80
105
130
160
Intermittent (3x441–480 V) [A]
44
57.2
71.5
88
115.5
143
176
Maximum input current
Continuous (3x380–440 V) [A]
41.8
57
70.3
84.2
102.9
140.3
165.6
Intermittent (3x380–440 V) [A]
46
62.7
77.4
92.6
113.1
154.3
182.2
Continuous (3x441–480 V) [A]
36
49.2
60.6
72.5
88.6
120.9
142.7
Intermittent (3x441–480 V) [A]
39.6
54.1
66.7
79.8
97.5
132.9
157
Maximum mains fuses
3.2.4.5 Recommendation of Fuses and Circuit Breakers
.
Estimated power loss [W], best
case/typical
(1)
496
734
995
840
1099
1520
1781
Weight enclosure protection rat-
ing IP54 [kg (lb)]
27 (59.5)
27 (59.5)
27 (59.5)
45 (99.2)
45 (99.2)
65 (143.3)
65 (143.3)
Efficiency [%], best case/typical
(2)
98
97.8
97.6
98.3
98.2
98.1
98.3
Output current at 50°C (122°F) ambient temperature
Continuous (3x380–440 V) [A]
35.2
48.8
58.4
63
74.2
102.9
123.9
AQ367426199594en-000101 / 130R0988
46 | Danfoss A/S © 2021.06
Specifications
VLT® HVAC Drive FC 131