3x380–480 V IP54
0.75 (1.0)
–
PKZM0-16
FRS-R-10
KTS-R-10
JKS-10
JJS-10
16
1.5 (2.0)
PKZM0-16
FRS-R-10
KTS-R-10
JKS-10
JJS-10
16
2.2 (3.0)
PKZM0-16
FRS-R-15
KTS-R-15
JKS-15
JJS-15
16
3.0 (4.0)
PKZM0-16
FRS-R-15
KTS-R-15
JKS-15
JJS-15
16
4.0 (5.0)
PKZM0-16
FRS-R-15
KTS-R-15
JKS-15
JJS-15
16
5.5 (7.5)
PKZM0-25
FRS-R-25
KTS-R-25
JKS-25
JJS-25
25
7.5 (10)
PKZM0-25
FRS-R-25
KTS-R-25
JKS-25
JJS-25
25
11 (15)
PKZM4-63
FRS-R-50
KTS-R-50
JKS-50
JJS-50
63
15 (20)
PKZM4-63
FRS-R-50
KTS-R-50
JKS-50
JJS-50
63
18.5 (25)
PKZM4-63
FRS-R-80
KTS-R-80
JKS-80
JJS-80
63
22 (30)
Moeller NZMB1-A125
–
FRS-R-80
KTS-R-80
JKS-80
JJS-80
125
30 (40)
FRS-R-125
KTS-R-125
JKS-125
JJS-125
125
37 (50)
FRS-R-125
KTS-R-125
JKS-125
JJS-125
125
45 (60)
Moeller NZMB2-A160
–
FRS-R-125
KTS-R-125
JKS-125
JJS-125
160
55 (70)
FRS-R-200
KTS-R-200
JKS-200
JJS-200
160
75 (100)
Moeller NZMB2-A250
–
FRS-R-200
KTS-R-200
JKS-200
JJS-200
200
90 (125)
FRS-R-250
KTS-R-250
JKS-200
JJS-200
200
3.2.5 EMC-compliant Electrical Installation
To ensure EMC-correct electrical installation, observe the following:
Use only shielded/armored motor cables and shielded/armored control cables.
Ground the shield at both ends.
Avoid installation with twisted shield ends (pigtails), because it reduces the shielding effect at high frequencies. Use the cable
clamps provided.
Ensure the same potential between the drive and the ground potential of PLC.
Use star washers and galvanically conductive installation plates.