6 Specifications
6.1 Mains Supply
6.1.1 3x380–480 V AC
Table 16: 3x380–480 V AC, 0.75–18.5 kW (1.0–25 hp), Enclosure Sizes I2–I4
Drive
PK75
P1K5
P2K2
P3K0
P4KO
P5K5
P7K5
P11K
P15K
P18K
Typical shaft output [kW]
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11
15
18.5
Typical shaft output [hp]
1.0
2.0
3.0
4.0
5.0
7.5
10.0
15
20
25
Protection rating IP54
I2
I2
I2
I2
I2
I3
I3
I4
I4
I4
Maximum cable size in terminals
(mains, motor) [mm
2
(AWG)]
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
16 (6)
16 (6)
16 (6)
Output current at 40°C (104°F) ambient temperature
Continuous (3x380–440 V) [A]
2.2
3.7
5.3
7.2
9.0
12
15.5
23
31
37
Intermittent (3x380–440 V) [A]
2.4
4.1
5.8
7.9
9.9
13.2
17.1
25.3
34
40.7
Continuous (3x441–480 V) [A]
2.1
3.4
4.8
6.3
8.2
11
14
21
27
34
Intermittent (3x441–480 V) [A]
2.3
3.7
5.3
6.9
9.0
12.1
15.4
23.1
29.7
37.4
Maximum input current
Continuous (3x380–440 V) [A]
2.1
3.5
4.7
6.3
8.3
11.2
15.1
22.1
29.9
35.2
Intermittent (3x380–440 V) [A]
2.3
3.9
5.2
6.9
9.1
12.3
16.6
24.3
32.9
38.7
Continuous (3x441–480 V) [A]
1.8
2.9
3.9
5.3
6.8
9.4
12.6
18.4
24.7
29.3
Intermittent (3x441–480 V) [A]
2.0
3.2
4.3
5.8
7.5
10.3
13.9
20.2
27.2
32.2
Maximum mains fuses
See
3.2.4.5 Recommendation of Fuses and Circuit Breakers
Estimated power loss [W], best
case/typical
(1)
21/
16
46/
57
46/
58
66/
83
95/
118
104/
131
159/
198
248/
274
353/
379
412/
456
Weight enclosure protection rat-
ing IP54 [kg (lb)]
5.3
(11.7)
5.3
(11.7)
5.3
(11.7)
5.3
(11.7)
5.3
(11.7)
7.2
(15.9)
7.2
(15.9)
13.8
(30.4)
13.8
(30.4)
13.8
(30.4)
Efficiency [%], best case/typical
(2)
98/
97.6
97.7/
97.2
98.3/
97.9
98.2/
97.8
98/
97.6
98.4/
98
98.2/
97.8
98.1/
97.9
98/
97.8
98.1/
97.9
Output current at 50°C (122°F) ambient temperature
Continuous (3x380–440 V) [A]
1.93
3.7
4.85
6.3
7.5
10.9
14
20.9
28
33
AQ367426199594en-000101 / 130R0988 | 45
Danfoss A/S © 2021.06
Specifications
VLT® HVAC Drive FC 131
Operating Guide