Parameter
Option/range
Default
Usage
N O T I C E
Changing this parameter affects the settings of other pa-
rameters.
Parameter 1-29
Automatic Mo-
tor Adaption
(AMA)
–
Off
Performing an AMA optimizes motor performance.
Parameter 1-30
Stator Resist-
ance (Rs)
0.000–9999.000 Ω
Size related
Set the stator resistance value.
Parameter 1-37
d-axis Induc-
tance (Ld)
0.000–1000.000 mH
Size related
Enter the value of the d-axis inductance. Obtain the value
from the permanent magnet motor datasheet.
Parameter 1-38
q-axis Induc-
tance (Lq)
0.000–1000.000 mH
Size related
Enter the value of the q-axis inductance.
Parameter 1-39
Motor Poles
2–100
4
Enter the number of motor poles.
Parameter 1-40
Back EMF at
1000 RPM
10–9000 V
Size related
Line-line RMS back EMF voltage at 1000 RPM.
Parameter 1-42
Motor Cable
Length
0–100 m
50 m
Enter the motor cable length.
Parameter 1-44
d-axis Induc-
tance Sat.
(LdSat)
0.000–1000.000 mH
Size related
This parameter corresponds to the inductance saturation of
Ld. Ideally, this parameter has the same value as
parameter
1-37 d-axis Inductance (Ld)
. However, if the motor supplier
provides an induction curve, enter the induction value,
which is 200% of the nominal current.
Parameter 1-45
q-axis Induc-
tance Sat.
(LqSat)
0.000–1000.000 mH
Size related
This parameter corresponds to the inductance saturation of
Lq. Ideally, this parameter has the same value as
parameter
1-38 q-axis Inductance (Lq)
. However, if the motor supplier
provides an induction curve, enter the induction value,
which is 200% of the nominal current.
Parameter 1-46
Position Detec-
tion Gain
20–200%
100%
Adjusts the height of the test pulse during position detec-
tion at start.
Parameter 1-48
Current at Min
Inductance for
d-axis
20–200%
100%
Enter the inductance saturation point.
Parameter 1-49
Current at Min
Inductance for
q-axis
20–200%
100%
This parameter specifies the saturation curve of the d- and q-
inductance values. From 20–100% of this parameter, the in-
ductances are linearly approximated due to
parameter 1-37
d-axis Inductance (Ld)
,
parameter 1-38 q-axis Inductance (Lq)
,
parameter 1-44 d-axis Inductance Sat. (LdSat)
, and
parameter
1-45 q-axis Inductance Sat. (LqSat)
.
AQ367426199594en-000101 / 130R0988
34 | Danfoss A/S © 2021.06
Programming
VLT® HVAC Drive FC 131
Operating Guide