Normal overload 110% for 1 minute
Frequency converter
TypicalShaft Output [kW]
P11K
11
P15K
15
P18K
18.5
P22K
22
P30K
30
P37K
37
P45K
45
P55K
55
P75K
75
P90K
90
Typical Shaft Output [HP] at
575 V
10
16.4
20.1
24
33
40
50
60
75
100
IP21/NEMA 1
B2
B2
B2
B2
B2
C2
C2
C2
C2
C2
IP55/NEMA 12
B2
B2
B2
B2
B2
C2
C2
C2
C2
C2
Output current
Continuous (3x525-550 V)
[A]
14
19
23
28
36
43
54
65
87
105
Intermittent (3x525-550 V)
[A]
15.4
20.9
25.3
30.8
39.6
47.3
59.4
71.5
95.7
115.5
Continuous (3x551-690 V)
[A]
13
18
22
27
34
41
52
62
83
100
Intermittent (3x551-690 V)
[A]
14.3
19.8
24.2
29.7
37.4
45.1
57.2
68.2
91.3
110
Continuous kVA (550 V AC)
[kVA]
13.3
18.1
21.9
26.7
34.3
41
51.4
61.9
82.9
100
Continuous kVA (575 V AC)
[kVA]
12.9
17.9
21.9
26.9
33.8
40.8
51.8
61.7
82.7
99.6
Continuous kVA (690 V AC)
[kVA]
15.5
21.5
26.3
32.3
40.6
49
62.1
74.1
99.2
119.5
Max. input current
Continuous (3x525-690 V)
[A]
15
19.5
24
29
36
49
59
71
87
99
Intermittent (3x525-690 V)
[A]
16.5
21.5
26.4
31.9
39.6
53.9
64.9
78.1
95.7
108.9
Max. pre-fuses
1)
[A]
63
63
63
63
80
100
125
160
160
160
Additional specifications
Estimated power loss at
rated max. load [W]
4)
201
285
335
375
430
592
720
880
1200
1440
Max. cable size (mains,
motor, brake) [mm
2
]/(AWG)
2)
[35]/(1/0)
[95]/(4/0)
Weight IP21 [kg]
27
27
27
27
27
65
65
65
65
65
Weight IP55 [kg]
27
27
27
27
27
65
65
65
65
65
Efficiency
4)
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
Table 9.8 Mains Supply 3x525-690 V AC IP21-IP55/NEMA 1-NEMA 12
General Specifications and ...
Design Guide
154
Danfoss A/S © Rev. 06/2014 All rights reserved.
MG11BC02
9
9