7 Application Examples
7.1 Application Examples
7.1.1 Start/Stop
Terminal 18 = start/stop
5-10 Terminal 18 Digital Input
[8]
Start
Terminal 27 = No operation
5-12 Terminal 27 Digital Input
[0]
No operation
(Default
coast inverse
5-10 Terminal 18 Digital Input
=
Start
(default)
5-12 Terminal 27 Digital Input
=
coast inverse
(default)
12 13 18
37
130BA155.12
32
27
19
29
33 20
P 5-12 [0]
P 5-10 [8]
Start/Stop
+24V
Speed
Safe Stop
Start/Stop
[18]
Illustration 7.1 Terminal 37: Available only with Safe Stop
Function
7.1.2 Pulse Start/Stop
Terminal 18 = start/stop
5-10 Terminal 18 Digital Input
[9]
Latched start
Terminal 27= Stop
5-12 Terminal 27 Digital Input
[6] Stop
inverse
5-10 Terminal 18 Digital Input
=
Latched start
5-12 Terminal 27 Digital Input
=
Stop inverse
12
13
18
37
130BA156.12
32
27
19
29
33
20
P 5 - 12 [6]
P 5 - 10[9]
+24V
Speed
Start
Stop inverse
Safe Stop
Start (18)
Start (27)
Illustration 7.2 Terminal 37: Available Only with Safe Torque
Off Function
Application Examples
Design Guide
122
Danfoss A/S © Rev. 06/2014 All rights reserved.
MG11BC02