Mains Supply 3x380-480 V AC - Normal overload 110% for 1 minute
Frequency converter
Typical Shaft Output [kW]
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P4K0
4
P5K5
5.5
P7K5
7.5
Typical Shaft Output [hp] at 460 V
1.5
2.0
2.9
4.0
5.0
7.5
10
IP20/Chassis
(A2+A3 may be converted to IP21 using a conversion kit)
A2
A2
A2
A2
A2
A3
A3
IP55/NEMA 12
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
IP66/NEMA 12
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
Output current
130BA058.10
Continuous (3x380-440V) [A]
3
4.1
5.6
7.2
10
13
16
Intermittent (3x380-440V) [A]
3.3
4.5
6.2
7.9
11
14.3
17.6
Continuous (3x441-480V) [A]
2.7
3.4
4.8
6.3
8.2
11
14.5
Intermittent (3x441-480V) [A]
3.0
3.7
5.3
6.9
9.0
12.1
15.4
Continuous kVA (400 V AC) [kVA]
2.1
2.8
3.9
5.0
6.9
9.0
11.0
Continuous kVA (460 V AC) [kVA]
2.4
2.7
3.8
5.0
6.5
8.8
11.6
Max. cable size:
(mains, motor, brake)
[[mm
2
/AWG]
2)
4/10
Max. input current
130BA057.10
Continuous
(3x380-440 V) [A]
2.7
3.7
5.0
6.5
9.0
11.7
14.4
Intermittent
(3x380-440 V) [A]
3.0
4.1
5.5
7.2
9.9
12.9
15.8
Continuous
(3x441-480 V) [A]
2.7
3.1
4.3
5.7
7.4
9.9
13.0
Intermittent
(3x441-480 V) [A]
3.0
3.4
4.7
6.3
8.1
10.9
14.3
Max. pre-fuses
1)
[A]
10
10
20
20
20
32
32
Environment
Estimated power loss
at rated max. load [W]
4)
58
62
88
116
124
187
255
Weight enclosure IP20 [kg]
4.8
4.9
4.9
4.9
4.9
6.6
6.6
Weight enclosure IP21 [kg]
Weight enclosure IP55 [kg]
9.7/13.5
9.7/13.5
9.7/13.5
9.7/13.5
9.7/13.5
14.2
14.2
Weight enclosure IP66 [kg]
9.7/13.5
9.7/13.5
9.7/13.5
9.7/13.5
9.7/13.5
14.2
14.2
Efficiency
3)
0.96
0.97
0.97
0.97
0.97
0.97
0.97
Table 9.3 Mains Supply 3x380-480 V AC
General Specifications and ...
Design Guide
MG11BC02
Danfoss A/S © Rev. 06/2014 All rights reserved.
149
9
9