Symptom
Possible cause
Test
Solution
Motor speed
unstable
Possible incorrect parameter
settings.
Check the settings of all motor pa-
rameters, including all motor com-
pensation settings. For closed-loop
operation, check PID settings.
Check settings in
parameter group 1-6*
Load Depen. Setting
. For closed-loop
operation, check settings in
parameter
group 20-0* Feedback
.
Motor runs
rough
Possible overmagnetization.
Check for incorrect motor settings
in all motor parameters.
Check motor settings in
parameter
groups 1-2* Motor data
,
1-3* Adv Motor
Data
, and
1-5* Load Indep. Setting
.
Motor does not
brake
Possible incorrect settings in
the brake parameters. Ramp-
down times may be too short.
Check brake parameters. Check
ramp time settings.
Check
parameter groups 2-0* DC Brake
and
3-0* Reference Limits
.
Open power
fuses
Phase-to-phase short.
Motor or panel has a short phase-
to-phase. Check motor and panel
phases for shorts.
Eliminate any shorts detected.
Motor overload.
Motor is overloaded for the appli-
cation.
Perform start-up test and verify that
motor current is within specifications.
If motor current is exceeding the
nameplate full load current, the motor
can run only with reduced load. Re-
view the specifications for the applica-
tion.
Loose connections.
Perform pre-start-up check for
loose connections.
Tighten loose connections.
Mains current
imbalance
greater than 3%
Problem with mains power
(see
Alarm 4, Mains phase loss
description).
Rotate input power leads into the
AC drive 1 position: A to B, B to C, C
to A.
If imbalanced leg follows the wire, it is
a power problem. Check the mains
supply.
Problem with the AC drive.
Rotate input power leads into the
AC drive 1 position: A to B, B to C, C
to A.
If the imbalanced leg stays on same in-
put terminal, it is a problem with the
AC drive. Contact the supplier.
Motor current
imbalance
greater than 3%
Problem with motor or motor
wiring.
Rotate output motor cables 1 posi-
tion: U to V, V to W, W to U.
If the imbalanced leg follows the wire,
the problem is in the motor or motor
wiring. Check motor and motor wiring.
Problem with AC drive.
Rotate output motor cables 1 posi-
tion: U to V, V to W, W to U.
If the imbalanced leg stays on same
output terminal, it is a problem with
the unit. Contact the supplier.
AC drive accel-
eration prob-
lems
Motor data are entered incor-
rectly.
If warnings or alarms occur, refer to
the
Warnings and Alarms
section.
Check that motor data are entered
correctly.
Increase the ramp-up time in
parame-
ter 3-41 Ramp 1 Ramp Up Time
. In-
crease current limit in
parameter 4-18
Current Limit
. Increase torque limit in
parameter 4-16 Torque Limit Motor
Mode
.
AC drive decel-
eration prob-
lems
Motor data are entered incor-
rectly.
If warnings or alarms occur, refer to
the
Warnings and Alarms
section.
Check that motor data are entered
correctly.
Increase the ramp-down time in
pa-
rameter 3-42 Ramp 1 Ramp Down Time
.
Enable overvoltage control in
parame-
ter 2-17 Over-voltage Control
.
6.11 Maintenance and Service
To prevent breakdown, danger, and damage, examine the drive for loose terminal connections, excessive dust buildup, and worn
parts at regular intervals. Replace worn or damaged parts with Danfoss authorized parts. For service and support, contact the local
Danfoss supplier.