•
•
•
B
ack
Ca
nc
el
In
fo
OK
On
Alarm
Warn.
e
3
0
b
b
4
6
7
.1
2
Illustration 27: Status Indicator Lights
Table 19: Fault Types
Type of fault
Warning indicator light
Alarm indicator light
Warning
On
Off
Alarm
Off
On (flashing)
Trip lock
On
On (flashing)
e
3
0
b
p
0
8
6
.1
3
Status
0.0Hz 0.000kW 0.00A
0.0Hz
0
Earth Fault [A14]
Auto Remote Trip
1(1)
Illustration 28: Alarm Example
6.9.3 WARNING 1, 10 Volts Low
Cause
The control card voltage is less than 10 V from terminal 50. Remove some of the load from terminal 50, as the 10 V supply is overloa-
ded. Maximum 15 mA or minimum 590 Ω.
A short circuit in a connected potentiometer or incorrect wiring of the potentiometer can cause this condition.
Troubleshooting
Remove the wiring from terminal 50.
If the warning clears, the problem is with the wiring.
If the warning does not clear, replace the control card.
6.9.4 WARNING/ALARM 2, Live Zero Error
Cause
This warning or alarm only appears if programmed in
parameter 6-01 Live Zero Timeout Function
. The signal on 1 of the analog inputs
is less than 50% of the minimum value programmed for that input. Broken wiring or a faulty device sending the signal can cause
this condition.
Troubleshooting
Check connections on all analog mains terminals.
AQ434333248451en-000101 / 130R1286
48 | Danfoss A/S © 2023.01
Operating the Drive
VLT Ea4 Parallel Drive Modules
Operating Guide
Summary of Contents for VLT Ea4
Page 1: ...Operating Guide VLT Ea4 Parallel Drive Modules...
Page 2: ......
Page 74: ......
Page 75: ......