![Danfoss VLT Ea4 Operating Manual Download Page 15](http://html1.mh-extra.com/html/danfoss/vlt-ea4/vlt-ea4_operating-manual_3870291015.webp)
-
4 Mechanical Installation
4.1 Fastener Torque Ratings
N O T I C E
Apply the specified torque when tightening fasteners. Too low or too high torque when fastening an electrical connection results
in a bad electrical connection.
To ensure correct torque, use a torque wrench.
Table 1: Fastener Torque Ratings
Location
Bolt size
Torque [Nm (in-lb)]
Mains terminal
M10/M12
19 (168)/37 (335)
Motor terminal
M10/M12
19 (168)/37 (335)
Ground terminal
M8/M10
9.6 (84)/19 (168)
Load sharing terminal
M10/M12
19 (168)/37 (335)
Regen terminal
M10/M12
19 (168)/37 (335)
Relay terminal
–
0.5 (4)
Door/panel cover
M5
2.3 (20)
Heat sink access panel
M5
2.3 (20)
Serial communication cover
M5
2.3 (20)
AQ434333248451en-000101 / 130R1286 | 15
Danfoss A/S © 2023.01
Mechanical Installation
VLT Ea4 Parallel Drive Modules
Operating Guide