Terminal Parameter
Default setting Description
53
Parameter group 6-1* Analog In-
put 1
Reference
Analog input. For voltage (V) or current (mA).
54
Parameter group 6-2* Analog In-
put 2
Feedback
55
–
–
Common for analog input.
5.11.2 Relay Terminals
The relay terminals are on the top plate of the drive module. See
. Use an extended wiring harness to connect the relay
terminal of drive module 1 (the drive module on the far left) to the terminal blocks on the control shelf.
RELAY 1
RELAY 2
01 02 03
04 05 06
e
3
0
b
f1
5
6
.1
0
Illustration 15: Relay 1 and Relay 2 Terminals
Table 6: Relay 01 Terminal Descriptions
Terminal
Parameter
Default setting Description
01: common
Parameter 5-40 Function Relay
[0]
[0] No operation
Form C relay output. For AC or DC voltage and resistive
or inductive loads.
02: normally open
03: normally
closed
Table 7: Relay 02 Terminal Descriptions
Terminal
Parameter
Default setting Description
04: common
Parameter 5-40 Function Relay
[1]
[0] No operation
Form C relay output. For AC or DC voltage and resistive
or inductive loads.
05: normally open
06: normally
closed
5.11.3 Routing Control Cables
Make sure to use the provided wire pathway when routing the control wires from the bottom of the drive system cabinet to the
control terminal.
Procedure
Tie down and route all control cables at the bottom of the enclosure.
Isolate control cables from high-power cables in the drive.
Connect the shields in a proper way to ensure optimum electrical immunity.
When the drive is connected to a thermistor, ensure that the thermistor control cable is shielded and reinforced/double
insulated. A 24 V DC supply is recommended.
Connect the control cables to the relevant options on the control card. For more detail, see the relevant fieldbus instruc-
tions. The fieldbus cable must be tied down and routed along with the other control cables inside the unit.
All control terminals are on the control shelf below the LCP.
AQ434333248451en-000101 / 130R1286 | 31
Danfoss A/S © 2023.01
Electrical Installation
VLT Ea4 Parallel Drive Modules
Operating Guide